3 Installation Guide
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
102
Figure 3-74
Connecting the RS485 monitoring
----End
3.6.6 (Optional) Connecting the Water Leakage Sensor
Procedure
Step 1
Connect one end of the two-core cable for the water leakage sensor to the water leakage
sensor.
Install the water leakage sensor 0.5 m away from the cabinet. If there is a raised floor, install
the water leakage sensor under the raised floor and keep the water leakage sensor contact
downwards.
Step 2
Connect the water leakage sensor.
For upflow units: Route the cable through the cable hole at the bottom, and bind it along
the beam at the bottom of the cabinet.