Figure 3-34 Connecting the water inlet and outlet pipes (NetCol5000-C030/C032)
----End
3.8.3.2 Connecting Aluminum Plastic Pipes
Procedure
Step 1 Open the rear door and remove the air filter.
Step 2 Knock off the knock-out holes for the chilled water inlet and outlet pipes.
NO TICE
● Ensure that pipes and power cables are routed through separate holes.
● Do not prepare extra knock-out holes to avoid performance loss.
● In connecting the pipes, ensure that the aluminum plastic pipes are in proper
contact with the straight male connectors.
● In connecting the pipes, avoid violent shake.
● NetCol5000-C030/C032 need to make the holes for the chilled water inlet and
outlet pipes using a knife.
Step 3 Remove the water pipe plug using an open-end wrench.
Step 4 Apply screw thread sealant evenly on the connecting position of external screw
threads of the straight male connector, and use a torque wrench and a common
wrench in collaboration to secure the straight male connector to the connector on
the device.
Step 5 Install the sealing ring and nut at the end of the aluminum plastic pipe that ran
through the hole rubber ring.
Step 6 After the aluminum plastic pipe and the straight male connector are connected,
secure them to the aluminum plastic pipe with the installed sealing ring and nut.
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
3 Installation
Issue 03 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
57