A
Glycol Adding Requirements
●
Purchase glycol and corrosion inhibitor from a local qualified smart cooling
product installation company.
●
Determine the glycol volume concentration based on the lowest temperature
in record in the area.
●
As the glycol solution is toxic, avoid skin contact with the glycol solution and
splashing it into your eyes. Dispose of the glycol solution in accordance with
local laws.
●
To prevent glycol solution from corroding pipes and the heat exchanging coil,
corrosion inhibitor should be mixed into the glycol solution. For details about
the mixing schemes, consult glycol experts.
●
Check the quality of the glycol solution on a quarterly basis and evaluate the
anticorrosion effects. For details, consult local water treatment experts.
Table A-1 Glycol concentration requirements at lowest temperatures
Lowest Recorded Local
Temperature
Glycol Volume
Concentration
Freezing Point of Glycol
Mixed Solution to Be
Added
0°C
13.6%
–5°C
–5°C to 0°C
22%
–10°C
–10°C to –5°C
30%
–15°C
–15°C to –10°C
35%
–20°C
–20°C to –15°C
40%
–25°C
–25°C to –20°C
45%
–30°C
–30°C to –25°C
49%
–35°C
–35°C to –30°C
52%
–40°C
–40°C to –35°C
55%
–45°C