6 System Operation and Maintenance
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
162
Step 5
Set the value to 300 Pa for the new differential pressure switch. Install it in the reverse order
of
to
. Close the rear door after the installation.
Step 6
Power on the device, tap
Start
on the LCD home screen. Choose
Settings
>
Alarm
Settings
>
Main Board
. Check that
Air filter blocked
is
Allow
.
Step 7
Choose
Maint
>
Diagnostic Mode
>
Enter
, and set
Indoor fan
to
100%
.
Step 8
Block 100% air volume at the return air side using a plastic foam board or baffle plate, and
check whether the
Air filter blocked
alarm is generated. If so, the differential pressure switch
works properly. Then exit the diagnostic mode.
----End
6.4.7 Replacing the T/H Sensor
Prerequisites
The temperature and humidity (T/H) sensor needs to be replaced.
A spare T/H sensor of the same model is available and functional.
Context
Preparation: Maintain from the rear door.
Procedure
Step 1
Tap
Shutdown
on the LCD home screen.
Exercise caution because the device is still energized after it is shut down on the LCD.
Step 2
Open the rear door and remove the air filter.
Step 3
Remove the cable terminals from the RS485_IN and RS485_OUT ports on the T/H sensor.
Step 4
Pull out the T/H sensor upwards.