Figure 12-20 Changing a password
----End
12.16 How to Set Alarm Parameters
Prerequisites
Before setting the alarm parameters, get familiar with the relationship among
each parameter.
Configurations of temperature and humidity alarms and main board alarms for
the air cooled devices comply with the following relationships:
●
Power underfrequency alarm threshold < Power overfrequency alarm
threshold
●
Backup power underfrequency alarm threshold < Backup power
overfrequency alarm threshold
●
Supply air high temperature alarm thr 5°C ≤ Return air high
temperature alarm threshold
●
Supply air high temperature alarm thr 5°C ≤ Hot aisle high
temperature alarm threshold
●
Cold aisle high temperature alarm thr 5°C ≤ Hot aisle high
temperature alarm threshold
●
Cold aisle high temperature alarm thr 5°C ≤ Return air high
temperature alarm threshold
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
12 FAQ
Issue 08 (2021-09-17)
Copyright © Huawei Technologies Co., Ltd.
306