Figure 11-7 Separating the fan from the guard
Step 7 Remove the waterproof connector from the spare fan, as shown by (2) in
. Use a torque wrench to replace the hexagonal waterproof connector
delivered with the spare fan. The torque must be 3.75 N·m.
Step 8 Install the new fan in the sequence from
Step 9 After re-power on, on the home screen of the indoor unit, choose Maint >
Diagnostic Mode > Enter, and set the outdoor unit speed to 100%. After the
outdoor unit has run for 5 minutes, check that the outdoor fan is running properly
and no alarm is raised.
Step 10 After confirmation, set the outdoor unit speed to 0% and exit from the diagnostic
mode.
----End
11.4 Replacing a Differential Pressure Switch
Prerequisites
●
A differential pressure switch needs to be replaced.
●
A spare differential pressure switch of the same model is available and
functional.
●
Tool: Phillips screwdriver
Context
The differential pressure switch can be maintained only from the rear door.
Procedure
Step 1 Tap Shutdown on the controller home screen.
NO TICE
Exercise caution because the device is still energized after it is shut down on the
controller home screen.
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
11 Parts Replacement
Issue 08 (2021-09-17)