8.2 Outdoor Unit Routine Maintenance
CA UTION
● Perform the troubleshooting with the power off: If an exception is identified
and needs to be handled, you must power off the outdoor unit first.
● Check and perform the troubleshooting with the power off: Before checking
and exception handling, you must power off the outdoor unit first.
● In heavy snow situations, clean up snow from the fan, pipes, electric control
box, and low-temperature component of the outdoor unit in time.
8.2.1 Monthly Maintenance
Table 8-5 Monthly maintenance items
Item
Expected Result
Troubleshooting
Remarks
Refrigerant
pipe
The refrigerant
pipes are secured.
Secure the pipe
support.
Perform the
troubleshooting
with the power off.
All refrigerant pipes
are clean without
leaking and eroding.
Drain the
refrigerant, and
repair the leakage
on the pipe.
Perform the
troubleshooting
with the power off.
The thermal
insulator on the
refrigerant pipe is
not damaged.
Rewrap the thermal
insulator.
Perform the
troubleshooting
with the power off.
Condenser
The fins are not
pushed down.
Restore the fins by
using a wire brush.
Perform the
troubleshooting
with the power off.
The air intake
section of the
condenser and the
air exhaust section
of the fan are
unblocked.
Clean up obstacles
on the inlet and
outlet.
Perform the
troubleshooting
with the power off.
The fins are not
blocked.
Clean the fins.
Perform the
troubleshooting
with the power off.