NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
3 Installation Guide
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
51
Wrench an anchor bolt clockwise to elevate a cabinet, wrench an anchor bolt
counterclockwise to lower a cabinet. The leveling feet can be adjusted within a range of
0–8 mm.
To prevent damage caused by cabinet tilt, adjust all the leveling feet at the four corners
instead of one foot.
Before leveling the cabinet, use a measuring tape to check that the vertical distance
between the top of the cabinet and the floor is 2000±3 mm.
Do not remove the leveling feet as the reinstallation can be difficult when you need to use
them.
Figure 3-24
Leveling feet
3.8.3 (Optional) Installing the Enclosure Frame
Procedure
Step 1
Open the front door, cut off the cable ties binding the LCD cable, and disconnect the front
door ground cable. Then lift and remove the front door.
Install the enclosure frame on the front door side.
Step 2
Remove one bolt fastener, two cabinet connecting plates, and two hinges.
Step 3
Secure the enclosure frame to the front door frame using eight M5x10 tapping screws, and
secure the bolt fastener, cabinet connecting plates, and hinges to the enclosure frame.
Step 4
Pull the LCD signal cable until the door can be smoothly opened and closed, install the LCD
signal cable, and put back the NTC cable. Connect the ground cable under the front door to
the ground point marked on the enclosure frame.
Содержание NetCol5000-A021
Страница 234: ......