NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
5 Operation and Maintenance
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
208
Step 6
Power on the device and tap
Startup
on the home screen. Ensure that the air conditioner is
running normally without any alarms.
----End
5.4.16 Replacing the Switch
Prerequisites
The switch QF3 that controls the outdoor unit and compressor or the QF4 that controls
the electric heater, as shown in
, needs to be replaced.
A spare switch QF3 that controls the outdoor unit and compressor or the QF4 that
controls the electric heater of the same model is available and functional.
Tool: Phillips screwdriver
Procedure
Step 1
On the controller home screen, tap
Shutdown
, and turn off the air conditioner switch in the
PDC.
Exercise caution because the device is still energized after it is shut down on the controller
home screen.
Step 2
Open the rear door and remove the air filter.
Step 3
Open the front cover of the switch, as shown by (1) in
Содержание NetCol5000-A
Страница 264: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 265: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...