CA UTION
The wiring terminals must stay in good contact with the floats. Otherwise, the
condensate pump cannot start properly.
Figure 3-13 Removing the transport fasteners from the floats and connecting the
wiring terminals
NO TE
● The wiring terminal to the low float has been factory installed.
● Put away the removed rubber fixing objects. If the container is to be transported again,
remove the wiring terminal from the high float and reinstall them.
----End
3.4.2 Removing the Transport Fasteners from the Compressor
Context
CA UTION
When removing transport fasteners, do not remove the fuel return solenoid valve.
Otherwise, the solenoid valve might be burnt due to improper reinstallation.
Procedure
Step 1 Loosen the three bolts on the compressor using a 13# solid wrench, as shown in
.
NO TICE
Do not directly take the bolts out.
Step 2 Remove the transport fasteners.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
3 Installation Guide
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.