6.5.2.2.1 Setting Monitoring Parameters for a T/H Sensor (BOM Number:
33010346)
Prerequisites
●
The device address planned for the ambient temperature and humidity sensor
is obtained.
●
The ambient temperature and humidity sensor connects to the collector and
displays values on the display panel.
●
The IP address, user name, and password for logging in to the collector are
obtained.
●
A PC with an IP address in the same network segment as the collector is
prepared, and the PC connects to the collector over a switch.
Context
Before connecting the ambient temperature and humidity sensor to the NetEco,
set monitoring parameters, such as the device address and baud rate, on the
sensor, and then modify the port parameters for the collector connecting to the
sensor to ensure that the values of BaudRate, DataBit, StopBit, and Parity on the
sensor are consistent with those for the collector port.
Procedure
Step 1 Hold down Set on the display panel of the ambient temperature and humidity
sensor for 2 seconds.
Step 2 When Add is displayed, set the device address by pressing + and -. When creating
an ambient temperature and humidity sensor on the NetEco, set Device Address
to the same value.
Step 3 Press Set.
Step 4 When bAu is displayed, retain the default value or change the baud rate by
pressing + and -. Set BaudRate for the collector port to the same value.
NO TE
DataBit, StopBit, and Parity for the ambient temperature and humidity sensor cannot be
set on the WebUI. Their values are 8, 1, and None respectively.
Step 5 Set RS485 port parameters for the collector based on the value of BaudRate,
DataBit, StopBit, and Parity of the device. For ECC800-Pro collector settings, see
6.5.1.4 Setting RS485 Parameters for the ECC800-Pro Collector
----End
6.5.2.2.2 Creating a Temperature and Humidity Sensor on the NetEco
Prerequisites
●
You have the operation rights for Planning Configuration.
●
You have created a management domain for the device to be added on the
Planning Configuration page.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
6 Adding Devices
Issue 02 (2021-05-12)
Copyright © Huawei Technologies Co., Ltd.
253