Step 8 Click
on the toolbar to save the device information.
Step 9 Click Connection test to start the connection test.
----End
6.4.8 Adding a SmartLi
6.4.8.1 Setting SmartLi Monitoring Parameters (Modbus TCP)
Before connecting the SmartLi to the NetEco, set monitoring parameters such as
the IP address on the SmartLi.
Prerequisites
●
You have obtained the IP address, subnet mask, and default gateway planned
for the SmartLi.
●
The SmartLi is powered on.
Context
SmartLi model: SmartLi-512V-80AH-F-01
Procedure
Step 1 On the SmartLi LCD home screen, tap Settings.
Step 2 Enter the SmartLi password.
NO TE
The preset password is 000001.
Step 3 Choose Communication.
1. Set IP address assign to Manual, and set IP address, Subnet mask, and
Gateway.
2. Set ModbusTCP encryption to Enable.
NO TE
If Modbus TCP encryption is disabled on the device, SSL connection must be disabled
on the NetEco.
----End
6.4.8.2 Creating a SmartLi on the NetEco
This section describes how to create a SmartLi on the NetEco.
Prerequisites
●
You have the operation rights for Planning Configuration.
●
You have created a management domain for the device to be added on the
Planning Configuration page.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
6 Adding Devices
Issue 02 (2021-05-12)
Copyright © Huawei Technologies Co., Ltd.
219