iManager NetEco 6000
Device Installation and Commissioning Guide
7 Device Maintenance
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
269
Figure 7-9
Removing a smoke detector
Step 2
Remove the cables from the smoke detector and apply insulation measures such as wrapping
the cables with insulation tape to avoid hazards.
Step 3
Install a new smoke detector and reconnect the cables.
Step 4
Install the new smoke detector to the base by rotating it in a direction opposite to
Step 5
Blow smoke towards the smoke detector using a smoke pistol until the smoke detector
indicator changes from blinking once every 6s to steady on. If a smoke detector fire alarm is
triggered, the smoke detector is functional.
----End
7.2.5.4 Replacing an Infrared Sensor
Prerequisites
An ESD wrist strap, ESD gloves, ESD box or bag, door key, and required tools are
available.
The new infrared sensor is intact.
Procedure
Step 1
Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap and ESD
gloves.
Step 2
Disconnect the signal and power cables from the infrared sensor and record the cable
connection positions.
Step 3
Remove the infrared sensor from the support buckle.
Step 4
Connect the signal and power cables for the new infrared sensor according to the information
you recorded.
Step 5
Mount the new infrared sensor on the support buckle and adjust the sensor angle.
----End