7.1 Routine Maintenance
7.1.1 Monthly maintenance
7.1.1.1 Routine Maintenance for the Collector
Routine maintenance for the ECC500 collector is used as an example here. For the routine
maintenance for ECC800 collector, refer to section
Routine Maintenance
in ECC800 Data
Center Controller User Manual.
Table 7-1
Routine maintenance for the collector
Item
Mainte
nance
Frequen
cy
Method
Expected
Result
Symptom
and
Possible
Cause
Exception
Handling
Main
control
module
Monthly
Check
whether the
indicators on
the main
control
module are
normal.
The RUN
indicator
blinks at long
intervals (on
for 1s and
then off for
1s).
The ALM
indicator is
off.
The RUN
indicator is
off, indicating
that the main
control
module is in
poor contact
with the
ECC500, is
faulty, or has
no power
input.
Check that
the main
control
module is in
good contact
with the
ECC500, runs
properly, and
has normal
power input.