IDS1000 Container Data Center
User Manual
3 Power-On Commissioning
Issue 01 (2014-3-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
20
Figure 3-11
Power switches
Step 5
Unlock the keypad.
The keypad is locked to prevent misoperation. To unlock the keypad, press
/KEY ON/OFF
and then press
/QUERY TIME
. The keypad is unlocked and the keypad indicator is on. To
lock the keypad, press
/KEYON/OFF
. The keypad indicator is off. The key will be locked if
no operation is performed in 4 minutes.
Step 6
Start or stop the audible and visual alarm.
When the keypad is unlocked, press
/HORN/STROBE
to start or stop the audible and visual
alarm. After the audible and visual alarm is started, the indicator beside the button is on.
Step 7
Start or stop the alarm bell.
When the keypad is unlocked, press
/ALARM BELL
to start or stop the alarm bell. After the
alarm bell is started, the indicator beside the button is on.
Step 8
Check that all smoke detector and heat detector indicators work properly.
Normally, the indicators blink once every 6 seconds.
Step 9
Check that emergency startup/abort switch indicators work properly.
Normally, the Run indicator is steady on.
When powering on and commissioning the hardware of the fire extinguishing system, commission all
the fire extinguishing devices in the container data center. For details about the positions of each fire
extinguishing device, see the
Container Data Center Initial Configuration Guide
.
----End
3.4 Fire Extinguishing System Commissioning
Commission the fire extinguishing system before using the container data center to ensure that
the system works properly.