IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
3 Maintenance
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
41
Item
Method
Expected Result
Troubleshooting
containe
rs
connected
without damage
or misshapen.
Cable trays, screws, and
nuts are free from rust or
corrosion.
Repaint corroded cable trays,
or replace damaged and
seriously corroded parts. For
details, see the installation
guide for the corresponding
solution.
Cables
Check cable
connections.
Cables are securely
connected without bare
terminals.
Secure terminal connections,
and replace terminals that do
not meet requirements. For
details, see the installation
guide for the corresponding
solution.
Check whether
cables are intact.
Cable jackets are free
from damage or cracks.
No cable overheats due
to overload and the
loads are within the
rated capacity of the
cables (the cables
works only a very short
time under overload
situations).
The bend radius of
cables meets
requirements.
The cable armor is
intact.
Replace parts that do not
meet requirements.
3.5 Annual Maintenance
Table 3-20
Annual maintenance checklist
Categ
ory
Item
Method
Expected
Result
Troubleshooting
Power
supply
and
distrib
ution
system
PDC
Check whether
the PDC panels
are covered by
dust.
The white
paper that you
use to wipe the
cabinet panels
remains clean.
If the white paper becomes
dirty, clean the PDC.
NOTE
You are advised to clean the
power distribution equipment
only when the All-in-one or
power distribution equipment is
powered off for maintenance.