IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
3 Maintenance
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
31
3.4.2 Cooling System
Table 3-15
Semi-annual maintenance checklist for the cooling system
Item
Method
Expected
Result
Troubleshooting
Pipes
Check the safety
clamps.
Nuts on safety
clamps are
secure.
If a nut is loose, tighten it using a
hex key.
3.4.3 Monitoring System
Table 3-16
Semi-annual maintenance checklist for the monitoring system
Item
Method
Expected
Result
Troubleshooting
LAN switch View the LAN
switch power
indicator (PWR).
The PWR
indicator is
steady green.
None
If the indicator is
off, the power
supply unit
(PSU) is not
detected, or the
power supply to
the board is
abnormal when
the switch is
configured with
one PSU.
Check the power supply. If the
power supply is normal, replace
by following instructions in
The PWR
indicator is
steady red.
If the PWR indicator is steady red:
Check whether two PSUs are
configured, and switch on the
power supply.
Check that the power supply is
switched on.
The power supply to the board
and the PoE power supply are
faulty. For details, see