6.2 Environmental Specifications
Table 6-2 Environmental specifications
Category
Specifications
Temperature
● Operating temperature: 5°C to 45°C (41°F to 113°F)
(ASHRAE Classes A2 to A4 compliant)
● Storage temperature (≤ 72 hours): –40°C to +65°C
(–40°F to +149°F)
● Long-term storage temperature (> 72 hours): 21°C
to 27°C (69.8°F to 80.6°F)
● Maximum temperature change rate: 20°C/h (36°F/h)
NOTE
The highest operating temperature varies depending on the
server configuration. For details, see
.
Relative humidity (RH,
non-condensing)
● Operating humidity: 8% to 90%
● Storage humidity (≤ 72 hours): 5% to 95%
● Long-term storage humidity (> 72 hours): 30% to
69%
● Maximum change rate: 20%/h
Air volume
≥ 204 cubic feet per minute (CFM)
Altitude
● Operating altitude ≤ 3050 m (10006.44 ft)
– If the server complying with ASHRAE Class A2 is
used in a place above 900 m (2952.76 ft), the
highest operating temperature decreases by 1°C
(1.8°F) for every increase of 300 m (984.25 ft).
– If the server complying with ASHRAE Class A3 is
used in a place above 900 m (2952.76 ft), the
highest operating temperature decreases by 1°C
(1.8°F) for every increase of 175 m (574.15 ft).
– If the server complying with ASHRAE Class A4 is
used in a place above 900 m (2952.76 ft), the
highest operating temperature decreases by 1°C
(1.8°F) for every increase of 125 m (410.10 ft).
● HDDs cannot be used at an altitude of over 3000 m
(9842.4 ft).
Corrosive gaseous
contaminant
Maximum corrosion product thickness growth rate:
● Copper corrosion rate test: 300 Å/month (meeting
level G1 requirements of the ANSI/ISA-71.04-2013
standard on gaseous corrosion)
● Silver corrosion rate test: 200 Å/month
Huawei FusionServer Pro 2288X V5 Server
Technical White Paper
6 Product Specifications
Issue 03 (2020-04-20)
Copyright © Huawei Technologies Co., Ltd.
64