FusionModule800 Smart Small Data Center
Maintenance Guide
5 Parts Replacement
Issue 02 (2016-11-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
70
Figure 5-32
Removing an electric heater
Step 6
Install the new electric heater in the original position by performing the preceding steps in
reverse order, and install the fan and air director (if there is any).
Step 7
Clear up the electric heater total runtime.
Method 1: Log in to the ECC800 mobile phone or pad app as admin.
a.
Choose
Home
.
b.
Tap the cabinet that houses the air conditioner in the micro-module view.
c.
Tap the air conditioner to be set in the cabinet layout diagram.
d.
Choose
Real-time Data
>
Perf Maint
, clear up the electric heater total running
time.
Method 2: Log in to the ECC800 WebUI as admin. Choose
Monitoring
>
Air
Conditioner
>
NetCol5000-A0104
>
Controls
>
Performance Maint Ctrl
, clear up the
electric heater total running time.
----End
5.3.1.7 Replacing a Liquid Level Detector
Prerequisites
Tools: adjustable wrench, diagonal pliers or scissors.
A liquid level detector needs to be replaced.
A spare liquid level detector of the same model is available and functional.
Context
A liquid level detector is composed of the conductor outer jacket, liquid level detector, switch,
and card pole. A liquid level detector rises or drops as the liquid level changes due to the