FusionModule800 Smart Small Data Center
Installation Guide (Six Fans)
3 Hardware Installation
Issue 10 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
40
Figure 3-16
Positioning bolt on an air director
(1) Positioning bolt
----End
3.3 Adjusting the Positions of Aisle Side Sealing Plates
Context
The Converged Cabinet has been configured with aisle side sealing plates on both sides
before delivery. The Converged Cabinet is often placed in the middle of the Smart
Module. Therefore, to ensure smooth airflow in the Smart Module, remove the aisle side
sealing plates from the Converged Cabinet before installing the cabinet.
The IT cabinet is not configured with aisle side sealing plates before delivery. If you
need to place the IT cabinet at the end of a row, install an aisle side sealing plate on the
cabinet side towards the aisle exterior.
Totally there are two aisle side sealing plates to be removed from the Converged Cabinet.
Each end cabinet needs to be installed with one aisle side sealing plate.
Procedure
Step 1
Remove the sealing plate at the aisle side from the Converged Cabinet, as shown in