FusionModule5000 Smart Modular Data Center
Commissioning Guide
6 Commissioning the Management System
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
62
6.5 Commissioning the AC Actuator (Wireless
Networking)
If an AC actuator with wireless networking is configured, perform the following steps to set
its parameters.
Prerequisites
The upstream power input circuit breaker of the AC actuator is turned on.
Procedure
Step 1
Log in to the ECC800 WebUI as an administrator.
Before networking, ensure that both the ECC800 and AC actuator have no network
parameters. That is, the RF_Z indicators on the ECC800 and AC actuator are both steady
green.
If the RF_Z indicator on the ECC800 is not steady green, hold down the SW button on
the ECC800 for more than 6 seconds to make the ECC800 enter non-networking status.
If the RF_Z indicator on the AC actuator is not steady green, hold down the BLINK
button on the AC actuator for more than 10 seconds to make the AC actuator enter
non-networking status.
1.
Hold down the SW button on the ECC800 main control module for 2 seconds (1.2–5
seconds allowed). The RF_Z indicator on the ECC800 main control modules turns from
steady green to blinking green at super short intervals (blinking at 10 Hz, on for 0.05
seconds and then off for 0.05 seconds). The ECC800 enters the wireless networking
(802.15.4) pairing status.
2.
Hold down the BLINK button on the AC actuator for 2 seconds (1–5 seconds allowed).
The RF_Z indicator on the AC actuator turns from steady green to blinking green
intermittently at super short intervals (blinking at super short intervals for 0.5 second and
then off for 0.5 second). The component enters the wireless network search status.
3.
After the wireless networking (802.15.4) pairing succeeds, the RF_Z indicator on the AC
actuator starts to blink at long intervals.
4.
After all AC actuators are networked, hold down the SW button on the ECC800 main
control module for 2 seconds (1.2–5 seconds allowed). The RF_Z indicator on the
ECC800 main control modules turns from blinking green at super short intervals to
blinking green at long intervals (blinking at 0.5 Hz, on for 1 second and then off for 1
second). The ECC800 exits the wireless networking (802.15.4) pairing status.
If two or more ECC800 controllers need to be networked in wireless (802.15.4) mode, only one system
can be networked at one time. During the networking, ensure that the RF_Z indicators on the ECC800
main control modules of other systems are blinking at long intervals or steady on.
Step 2
Set running parameters for the AC actuator.
Table 6-5
Setting AC actuator parameters
Path
Operation
Monitoring
>
Aisle
>
AC Actuator
Group
>
AC Actuator n
>
Running
Set
Route 1 Control Mode
to
Light
, and
click
Submit
.