FusionModule5000 Smart Modular Data Center
Commissioning Guide
6 Commissioning the Management System
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
60
----End
Follow-up Procedure
To modify or delete the email parameter settings, click
Modify
or
Delete
.
6.4 Commissioning the Smart Busway
Context
If the smart busway is used, general input units and power distribution units communicate
with the ECC800 using the Modbus-MAC protocol. After the general input units and power
distribution units properly connect to the ECC800, the ECC800 automatically identifies the
units.
Then, you need to set parameters for the general input units and power distribution units;
otherwise, a false alarm may be generated.
Procedure
Step 1
Set parameters for general input units on the ECC800 WebUI.
1.
Set parameters for general input unit 1.
Table 6-3
Power distribution settings for a general input unit
Path
Parameter
Name
Default
Value
Setting
Monitoring
>
Power
Distribution
>
General
Input Unit1
>
Running
Parameters
>
Power
Distribution Settings
Rated system
frequency
50
Set based on actual
conditions.
Rated system
voltage
380
Set based on actual
conditions.
Rated system
current
250
Set based on actual
conditions.
NOTE
The value should be
consistent with the
information on the nameplate
of the general input unit.
If the model is
NMW-0250AC, set
Rated
system current
to
250 A
.
If the model is
NMW-0160AC, set
Rated
system current
to
160 A
.
System CT ratio
250
Set based on actual
conditions.
If
Rated system
current
is 250 A, set