FusionModule5000 Smart Modular Data Center
Commissioning Guide
7 FAQ
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
112
3.
Click
Test Connect
to check whether the T/H sensor connects to the ECC800 properly.
−
If the T/H sensor connects to the ECC800 properly, click
Confirm
. The connected
devices are displayed in the
Number of connected devices
list.
−
If the T/H sensor does not connect to the ECC800 properly, check whether the cable
between the T/H sensor and the ECC800 is connected properly, whether the T/H
sensor and ECC800 are running properly, and whether the input parameters are
consistent with the T/H sensor parameters.
Step 3
Check functions of the T/H sensor.
Table 7-10
Function check
Check Method
Normal Connection Status
Check the running information
about the T/H sensor on the
WebUI.
Choose
Monitoring
>
Aisle
>
T/H Sensor Group
>
T/H Sensorn
>
Running Info
, and check the current
T/H information of the cabinet.
Set T/H sensor alarm thresholds.
Choose
Monitoring
>
Aisle
>
T/H Sensor Group
>
T/H Sensorn
>
Running Parameters
, and set
High
temperature alarm threshold
,
Low temperature
alarm threshold
,
High humidity alarm threshold
,
and
Low humidity alarm threshold
as required.
NOTE
The default values of
High temperature alarm threshold
,
Low temperature alarm threshold
,
High humidity alarm
threshold
, and
Low humidity alarm threshold
are
30.0°C
,
5.0°C
,
85.0% RH
, and
15.0% RH
, respectively.
----End
7.1.7 How to Manage WebUI Users
Context
WebUI users are classified as
Administrator
and
Operator
. They have different operation
rights.
Administrator: The user name is
admin
and preset password is
Changeme
. The
administrator has all rights, including the rights for user management, browsing and
modifying all parameters in the system, software upgrade, and data import and export.
Operator: The user name is
operator
and preset password is
Changeme
. Operator has
no rights for user management, system setting, version upgrade, running parameters,
smart module plan view editing, and internal fault information exporting.
Procedure
Step 1
Change the login password.
1.
Log in to the ECC800 WebUI as an administrator.
2.
Choose
Maintenance
>
User Management
. The user management page is displayed.