![Huawei FusionModule500 Скачать руководство пользователя страница 119](http://html.mh-extra.com/html/huawei/fusionmodule500/fusionmodule500_user-manual_168046119.webp)
Table 4-12 DIP switch settings on T/H sensors
Address
DIP Switch Sequence No.
1
2
3
4
5
6
1
ON
OFF
OFF
OFF
OFF
OFF
2
OFF
ON
OFF
OFF
OFF
OFF
NO TICE
The default address of T/H sensors purchased from Huawei is 1.
----End
4.2.6.4 Installing T/H Sensors
Procedure
Step 1 Install T/H sensors.
1. Open the front and rear doors of the cabinet.
2. Unpack the two T/H sensors and attach one sensor to the mounting bars at
the 40th U position on the front door and the other to the 34th U position on
the rear door of the cabinet.
NO TE
The installation positions of the T/H sensors can be adjusted as required.
Step 2 Set the DIP switch address of the T/H sensor on the front door to 2 and that of
the T/H sensor on the rear door to 1.
Table 4-13 DIP switch setting on a T/H sensor
Address
DIP Switch Sequence No.
1
2
3
4
5
6
1
ON
OFF
OFF
OFF
OFF
OFF
2
OFF
ON
OFF
OFF
OFF
OFF
NO TICE
The default address of T/H sensors purchased from Huawei is 1.
----End
FusionModule500 Smart Mini Data Center
User Manual
4 Installation Guide
Issue 02 (2020-12-25)
Copyright © Huawei Technologies Co., Ltd.
109