FusionModule2000 Smart Modular Data Center
Product Description
5 Power Supply and Distribution System
Issue 06 (2020-05-21)
Copyright © Huawei Technologies Co., Ltd.
34
Silk
Screen
Description
Status
Initial Status
EPO_NC
EPO port
If the normally closed
(NC) port is
disconnected from the
EPO_12V port, EPO
is triggered.
Connected
EPO_12V
+12 V
SWITCH
STATUS_
OUT
Port for monitoring the UPS
output circuit breaker
Connected: circuit
breaker ON
Disconnected:
circuit breaker
OFF
Connected
SWITCH
STATUS_
0V
Port for signal ground
SWITCH
STATUS_
MT
Port for monitoring the
maintenance circuit breaker
Disconnected:
circuit breaker ON
Connected: circuit
breaker OFF
Disconnected
SWITCH
STATUS_
0V
Port for signal ground
SWITCH
STATUS_
BP
Port for monitoring the
bypass input circuit breaker
Connected: circuit
breaker ON
Disconnected:
circuit breaker
OFF
Connected
SWITCH
STATUS_
0V
Port for signal ground
SPD
Port for monitoring the
input AC surge protective
device (SPD)
Connected: SPD
enabled
Disconnected:
SPD disabled
Connected
0V
Port for signal ground
The dry contact interface card takes effect only after it is set on the monitoring system. Set the
unused dry contact signal to the unused status.
Set the EPO port to NO or NC as required.
When multiple UPSs are paralleled, all dry contact signals to be used need to connect to each UPS.
Single cables require dual-insulated twisted cables. If the length of a power cable is within 25–50 m,
its cross-sectional area must be 0.5 mm
2
to 1.5 mm
2
.
5.2.1.4.4 Monitoring Interface Card