5.8 Water Intrusion Alarm
Fault
Category
Alar
m
Sever
ity
Symptom
Possible
Cause
Troubleshooting
Water
Intrusion
Alarm
Gener
al
There is no water
onsite.
The water
sensor is faulty.
For details, see
Replacing a Water
Sensor (Rope Type)
6.3.2 Replacing a Water
Sensor (Point Type)
There is water
onsite.
A pipe is
damaged.
Contact Huawei
technical support.
A humidity
water refill pipe
is damaged.
Replace by following
instructions in
Replacing the
Humidifier Water Refill
Pipe for a Precision Air
Conditioner
The condensate
drainpipe is
damaged.
Replace by following
instructions in
Replacing the
Condensate Drainpipe of
a Precision Air
Conditioner
The condensate
drainpipe is
blocked.
Remove the drainpipe
outside the container,
and dig out the material
blocking the pipe using a
thin iron wire.
The
dehumidifier
drainpipe is
damaged.
Replace the dehumidifier
drainpipe.
The thermal
insulation layer
is damaged.
Replace by following
instructions in
Replacing a Thermal
Insulation Layer
The water sensor is
covered by
condensate water.
The humidity is
too high.
Dehumidify the
FusionModule1000
using a dehumidifier.
Condensate water
cannot be drained.
The condensate
drainpipe is
blocked or
Remove foreign matters
using a thin iron wire or