![Huawei FusionDC1000A Скачать руководство пользователя страница 43](http://html.mh-extra.com/html/huawei/fusiondc1000a/fusiondc1000a_maintenance-manual_168032043.webp)
Item
Method
Check Standard
Troubleshooting
Check whether the
ambient
temperature,
humidity, and solar
radiation outside the
prefab. module meet
requirements.
The external temperature,
humidity, and solar
radiation requirements of
the FusionDC1000 are as
follows:
● Temperature:
– Normal temperature:
–20°C to +55°C
– Low temperature: –
40°C to +45°C
● Humidity: 5%–95% RH
● Solar radiation: ≤ 1120
W/m
2
For details, contact Huawei
technical support.
3.5 Quarterly Maintenance
3.5.1 Power Supply and Distribution System
Table 3-9 Quarterly maintenance checklist for the power supply and distribution system
Device
Method
Check Standard
Maintenance Guide
SmartLi
Battery module
appearance
The battery modules are
clean.
Clean the battery
modules using dry cotton
cloth. Exercise caution
when cleaning a battery
module because its
voltage is high.
Connections
Each terminal is securely
connected.
Check the bolt at every
terminal. If any bolt is
loose, tighten it.
3.5.2 Monitoring System
Table 3-10 Quarterly maintenance checklist for the monitoring system
Check Item
Operation
Check Standard
Troubleshooting
Access
actuator
Power input
Input voltage: 36–60 V DC
Check the input power
cables if the input voltage
is abnormal.
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario)
3 Routine Maintenance
Issue 01 (2021-04-20)
Copyright © Huawei Technologies Co., Ltd.
35