3.4.3 Monitoring System
Table 3-5 Monthly maintenance checklist for the monitoring system
Check Item
Content
Check Standard
Troubleshooting
Access
actuator
Power input
Input voltage: 36–60 V DC
Check the input power cables
if the input voltage is
abnormal.
PWR indicator
Steady on: The power supply is
normal.
Off: No power supply is
available.
Check the input power cables.
ALM indicator
Steady on: A fault alarm is
generated.
Off: No fault alarm is
generated.
Clear alarms by referring to
the ECC800-Pro documents.
RUN indicator
Off: The power supply is
abnormal.
Blinking at long intervals: The
device successfully registers
with the ECC800-Pro and the
software runs properly (the
indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).
Blinking at short intervals: The
communication is disconnected
or the device fails to register
with the ECC800-Pro (the
indicator blinks at 4 Hz, on for
0.125s and then off for 0.125s).
Blinking: The indicator blinks at
super short intervals for 0.5s
(blinking at 10 Hz, on for 0.05s
and then off for 0.05s) and
then turns off for 0.5s. The
cycle lasts for 10s.
Check the power supply.
If the RUN indicator blinks
fast, check whether the
communications cable is
normal. If not, replace the
cable.
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario)