NO TICE
Exercise caution because the unit is still energized after it is shut down on the
home screen of the display module.
Step 2 Open the maintenance door, remove the cover of the water pump connection box,
and remove the cables.
Step 3 Remove the water pump.
1. Remove the water inlet and outlet pipes of the water pump.
2. Remove the fasteners from the water pump using a socket wrench, and pull
out the pump.
Figure 12-45 Removing a water pump
Step 4 Install the new pump on the smart cooling product and install the water pump
cables, and connection box cover.
Step 5 Power on the unit, choose Maint > Performance Maint on the home screen of
the display module to access the performance maintenance screen, and clear the
total runtime of the spray pump.
Step 6 Tap Start on the home screen. Ensure that the unit is running normally without
any alarms.
----End
12.21 Replacing a Switch
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
12 Component Replacement
Issue 03 (2021-04-20) Copyright © Huawei Digital Power Technologies Co., Ltd.
195