Figure 12-12 Removing a T/H sensor
Step 5 Disconnect the cable from the T/H sensor.
Step 6 Slide and remove the T/H sensor.
Step 7 Install the new T/H sensor and reconnect the cable.
NO TICE
Before installing the new T/H sensor, check that its DIP switch settings are
consistent with the DIP switch settings of the old T/H sensor.
Step 8 Power on the unit and tap Start on the home screen. Ensure that the unit is
running normally without any alarms.
----End
12.8 Replacing a T/H Sensor (FDC Scenario)
Prerequisites
●
A T/H sensor needs to be replaced.
●
A spare T/H sensor of the same model is available and functional.
●
Tools: Phillips screwdriver, scissors
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
12 Component Replacement
Issue 03 (2021-04-20) Copyright © Huawei Digital Power Technologies Co., Ltd.
162