whether the parameter settings are consistent with the independent
deployment AI_DI unit parameters.
----End
8.1.7.27 How Can I Set and Add a UIM20A Expansion Module (Modbus-TCP)?
Prerequisites
Connect one end of a network cable to the PoE port on the UIM20A expansion
module and the other end to the LAN port on the ECC800-Pro or the PoE port on
the smart ETH gateway.
NO TE
Cascading of UIM20A expansion modules is not supported.
Context
The UIM20A expansion module supports self-discovery and does not need to set
parameters.
Procedure
Step 1 Set the running parameters and control parameters for the UIM20A expansion
module on the WebUI.
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Choose Monitoring > System > UIM Group > UIMn.
3. On the Running Parameters tab page, set UIM20A expansion module
running parameters.
4. On the Controls tab page, set the UIM20A expansion module control
parameters.
----End
8.1.7.28 How Can I Set and Add a Multi-functional Sensor?
If a multi-functional sensor is installed, perform the following steps to configure it.
Prerequisites
One end of the straight-through cable has been connected to the PoE port on the
multi-functional sensor, and the other end has been connected to the PoE port on
the smart ETH converter.
Procedure
Step 1 Set multi-functional sensor parameters.
On the WebUI, choose Monitoring > Aisle > Multi-Func Sensor Group > Multi-
Func Sensor1 > Running Parameters, ensure that Smoke enable and Temp
enable are set to Enable, set High temperature alarm threshold and other
parameters as required, and then click Submit.
ECC800 Data Center Controller
User Manual (for ECC800-Pro)
8 FAQ