2. Choose Settings > Comm Settings > IP Settings, set IP assigning mode to
Automatic(DHCP), and tap Submit.
3. Choose Settings > Comm Settings > Modbus Settings, and set Connection
mode to Server and client, Server encryption to Enable.
NO TE
● After setting parameters for the NetCol5000-C(030, 032), the ECC800-Pro discovers the
access from the smart cooling product automatically.
● The earlier version has Protocol setting on the screen. The actual screen prevails.
Step 2 Set the running parameters and control parameters for the NetCol5000-C(030,
032) on the WebUI.
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Choose Monitoring > Cooling > NetCol5000-C0301.
NO TE
1 in NetCol5000-C0301 is variable and subject to change with the smart cooling
product model and connection sequence. The displayed value prevails.
3. On the Running Parameters tab page, set smart cooling product running
parameters.
4. On the Controls tab page, set the smart cooling product control parameters
(such as on/off control parameters).
CA UTION
After the smart cooling product is shut down, the temperature of the smart
module increases and data running is affected. Exercise caution when
performing this operation.
----End
8.1.7.24 How Can I Set and Add a NetCol5000-C030 (Modbus RTU)?
Prerequisites
One end of the straight-through cable has been connected to the J73
communications port on the NetCol5000-C030 main control board, and the other
end has been connected to the COM port on the ECC800-Pro collector or ETH
converter.
Procedure
Step 1 Set NetCol5000-C030 monitoring parameters.
1. Enter the NetCol5000-C030 home page, click Settings, choose the user name
Admin and enter password 000001. After login, the settings screen of the
NetCol5000-C030 is displayed.
2. Choose Settings > Comm Settings > Modbus Settings, choose Baud rate to
9600 and set Comm address to 1.
ECC800 Data Center Controller
User Manual (for ECC800-Pro)
8 FAQ
Issue 02 (2020-09-07)
Copyright © Huawei Technologies Co., Ltd.
291