2. Choose Comm Settings > IP Settings, set IP assigning mode to Automatic
(DHCP), and click Submit.
3. Choose Settings > Comm Settings > Modbus Settings, and set Connection
mode to Server and client, Server encryption to Enable.
NO TE
After the NetCol5000-A025 parameters are set, the ECC800-Pro can automatically identify
the automatic access of the NetCol5000-A025.
Step 2 Set the running parameters and control parameters for the 25 kW smart cooling
product on the ECC800-Pro WebUI.
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Choose Monitoring > Cooling > NetCol5000-A0251.
NO TE
– 1 in NetCol5000-A0251 is variable and subject to change with the smart cooling
product model and connection sequence. The displayed value prevails.
3. On the Running Parameters tab page, set running parameters.
4. On the Controls tab page, set the smart cooling product control parameters
(such as on/off control parameters).
CA UTION
After the smart cooling product is shut down, the temperature of the smart
module increases and data running is affected. Exercise caution when
performing this operation.
----End
8.1.7.23 How Can I Set and Add a NetCol5000-C(030, 032)/NetCol5000-
C(065, 080) Parameters (over Modbus TCP)?
Prerequisites
One end of the straight-through cable has been connected to the FE port on the
NetCol5000-C(030, 032) or the NetCol5000-C(065, 080) main control board, and
the other end has been connected to the POE port on the ETH converter.
Context
The following describes how to set and add a NetCol5000-C(030, 032).
Procedure
Step 1 Set NetCol5000-C(030, 032) monitoring parameters.
1. Enter the NetCol5000-C(030, 032) home page, click Settings, choose user
name admin and enter password 000001. After login, the settings screen of
the NetCol5000-C(030, 032) is displayed.