Path
Parameter
Setting
parameters
for adding
devices are
displayed.
Connect To
Select ECC800 from the drop-down list
box.
Communicati
ons Port
Select COM1 from the drop-down list box.
NOTE
The setting example indicates that the
PDU2000 is connected to the COM1 port on the
ECC800-Pro. If the PDU2000 is connected to
another port, enter the number of the
connected port.
Device
Address
Enter the actual device address of the
PDU2000.
3. Click Test Connect to check whether the PDU2000 connects to the ECC800-
Pro properly.
–
If the PDU2000 connects to the ECC800-Pro successfully, click Confirm.
The connected devices are displayed in the Number of connected
devices list.
–
If the connection fails, check whether the PDU2000 is properly connected
to the ECC800-Pro, whether the PDU2000 and ECC800-Pro are running
properly, and whether the parameter settings are consistent with the
PDU2000 parameters.
----End
8.1.7.16 How Can I Set and Add an ATS?
Prerequisites
One end of the straight-through cable has been connected to the COM port on
the ATS, and the other end has been connected to the COM port on the ECC800-
Pro collector or ETH converter.
Context
The ATS (ABB) model is OMD800.
Procedure
Step 1 Set the ATS device address. On the ATS display panel, press
, choose Device
Configuration > Modbus and set the device address.
NO TE
● The ATS device address is 1 by default.
● The initial password is 0001 for the ATS display panel.
Step 2 Add an ATS.
1. Log in to the ECC800-Pro WebUI as an administrator.
ECC800 Data Center Controller
User Manual (for ECC800-Pro)
8 FAQ
Issue 02 (2020-09-07)
Copyright © Huawei Technologies Co., Ltd.
281