ECC500
User Manual
5 UI Description
Issue 05 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
79
Parameter
Setting
Communication
Board COM
Select
2
from the drop-down list box.
NOTE
The setting example indicates that the PD510 coulometer is connected to
the COM2 port of the RS485 card in slot 3 of the ECC500. If the PD510
coulometer is connected to another port, set the number of the connected
port.
Equipment Address
In this example, set
Equipment Address
to
1
. Set the actual
device address of the PD510 coulometer during operations.
Timeout
The default timeout interval is 2s. Set the parameter to the required
value.
Step 4
Click
Add Equipment
.
----End
Follow-up Procedure
If the device addition fails, check whether the settings are consistent with the device
parameters.
5.2.10 Adding a Networked Device
Prerequisites
A networked device is connected to the ECC500 over a switch. The device and ECC500
have been powered on.
You have obtained the IP address of the networked device.
You have obtained the ECC500 IP address as well as the user name and password for
WebUI login.
You have prepared a PC which is in the same IP address segment as the ECC500 and
connected the PC to the ECC500 over a switch.
Context
Networked devices, such as ATMs, are devices with the same IP attributes in an equipment
room or site. By adding a networked device, you connect the device to the ECC500 in the
same network so that the ECC500 monitors the device status. If the networked device is
offline, the ECC500 will report a disconnection alarm on its WebUI.
Procedure
Step 1
On a PC which is in the same IP address segment as the ECC500, enter
https://
XX.XX.XX.XX
in the address box, and press
Enter
.
XX.XX.XX.XX
indicates the ECC500 IP address.