ECC500
User Manual
5 UI Description
Issue 05 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
68
Figure 5-17
Adding a UPS5000-E
Table 5-4
UPS5000-E parameters
Parameter
Setting
Communication
Board Slot
Select
3
from the drop-down list box.
NOTE
The setting example indicates that the UPS5000-E is connected to the
COM2 port of the RS485 card in slot 3 of the ECC500. If the UPS5000-E
is connected to another port, set the slot number for the connected port.
Communication
Board COM
Select
2
from the drop-down list box.
NOTE
The setting example indicates that the UPS5000-E is connected to the
COM2 port of the RS485 card in slot 3 of the ECC500. If the UPS5000-E
is connected to another port, set the number of the connected port.
Equipment Address
In this example, set
Equipment Address
to
1
. Set the actual
device address of the UPS5000-E during operations.
Timeout
The default timeout interval is 2s. Set the parameter to the required
value.
Step 4
Click
Add Equipment
.
----End
Follow-up Procedure
If the device addition fails, check whether the settings are consistent with the device
parameters.