ECC500
User Manual
5 UI Description
Issue 05 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
62
5.2.3.4 Adding a Water Sensor
Prerequisites
You have obtained the ECC500 IP address as well as the user name and password for
WebUI login.
You have prepared a PC which is in the same IP address segment as the ECC500 and
connected the PC to the ECC500 over a switch.
Context
A water sensor should be connected to the AI/DI_4 port on the MUE05A4 of the
ECC500 by default. To connect the water sensor to another port, set the port parameters
using the following method.
A water sensor can be automatically identified. After it is connected to an AI/DI port on
the ECC500. The sensor type is automatically identified and displayed in A
I/DI_4
Sensor Type
on the ECC500 WebUI.
Procedure
Step 1
Log in to the ECC500 WebUI.
Step 2
Choose
Monitoring
>
MUE05A Expansion Card
>
MUE05A4
>
Running Parameter
>
AI/DI_4 Port Settings
.
Step 3
Set
AI/DI_4 Sensor
to
Enable
.
Step 4
Click
Submit
.
Step 5
Set
AI/DI_4 Sensor Name
, for example, to
Water_Sensor
.
Step 6
Check whether
Leak Sensor(NC)
is automatically displayed in
AI/DI_4 Sensor Type
.
Step 7
Set
AI/DI_4 Power Supply
to
On
.
Step 8
Click
Submit