ECC500
User Manual
4 Installation and Commissioning
Issue 05 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
47
Table 4-5
Mapping between device addresses and Modbus card DIP switch settings
Device
Address
Toggle
Switch 1
Toggle
Switch 2
Toggle
Switch 3
Toggle
Switch 4
Toggle
Switch 5
Toggle
Switch 6
Toggle
Switch 7
Toggle
Switch 8
1
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
2
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
3
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
4
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
----End
4.4.5 Setting the UPS5000-E Device Address
Prerequisites
You have obtained the device address assigned to the UPS5000-E.
The UPS5000-E has been powered on.
Procedure
Step 1
Tap
Settings
on the UPS5000-E home screen.
Step 2
Enter the administrator user name and password and tap
on the screen.
The preset user name and password for the UPS5000-E are respectively
Admin
and
000001
. To ensure
access security, change the password upon first use.
Step 3
Tap
Communication
.
Step 4
Set
RS485 address
and
RS485 baud rate
.
Table 4-6
Parameter description
Parameter
Setting
RS485 address
Indicates the device address assigned to the UPS5000-E. The
addresses of devices connected to a same port must be unique.
When creating a UPS5000-E on the ECC500 WebUI, enter this
value in
Equipment Address
.
RS485 baud rate
Retain the default value
9600
.
The
DataBit
,
StopBit
, and
Parity
for the UPS5000-E cannot be set on the WebUI. Their
default values are
8
,
1
, and
None
respectively.
----End