Installation prepare

1.

 

When installing or relocating the unit, be sure to keep the refrigerant circuit free

from air or substances other than the specified refrigerant.

— 

Any presence of air or other foreign substance in the refrigerant circuit will cause system      

     pressure rise or compressor rupture, resulting in injury.

2.

 

When installing or moving this unit, do not charge the refrigerant which is not

comply with that on the nameplate or unqualified refrigerant.

— 

Otherwise, it may cause abnormal operation, wrong action, mechanical malfunction or 

       

even series safety accident.

3.

 

When refrigerant needs to be recovered during relocating or repairing the unit,

be sure that the unit is running in cooling mode. Then, fully close the valve at high

pressure side (liquid valve). About 30-40 seconds later, fully close the valve at low

pressure side (gas valve), immediately stop the unit and disconnect power. Please

note that the time for refrigerant recovery should not exceed 1 minute.

— 

If refrigerant recovery takes too much time, air may be sucked in and cause pressure 

     rise or compressor rupture, resulting in injury.  

4.

During refrigerant recovery, make sure that liquid valve and gas valve are fully

closed and power is disconnected before detaching the connection pipe.

— 

If compressor starts running when stop valve is open and connection pipe is not yet 

     connected, air will be sucked in and cause pressure rise or compressor rupture, resulting 
     in injury.

To ensure safety, please be mindful of the following precautions.

WARNING

Safety precautions for installing and relocating the unit

Grounding requirement

1. The air conditioner is the first class electric appliance. It must be properly grounding with

specialized grounding device by a professional. Please make  sure it is always grounded
effectively, otherwise it may cause electric shock.

2. The yellow-green wire in air conditioner is grounding wire, which can't be used  for other

purposes.

3. The grounding resistance should comply with national electric safety regulations.
4. The appliance must be positioned so that the plug is accessible.
5. An all-pole disconnection switch having a contact separation of at least 3mm in all poles

should be connected in fixed wiring. For models with a power plug, make sure the plug is

within reach after installation.

Содержание HTWS026IX80SR32-I

Страница 1: ...TALLATION MANUAL INDOOR UNIT SPLIT ENGLSIH IX80S R32 HTWS026IX80SR32 I HTWS035IX80SR32 I HTWS052IX80SR32 I HTWS071IX80SR32 I Thanks for choosing our product Please read carefully this manual before us...

Страница 2: ...U To prevent possible harm to the environment or human health from uncontrolled waste disposal recycle it responsibly to promote the sustainable reuse of material resources To return your used device...

Страница 3: ...frigerant with no harm to the ozonosphere The influence upon the greenhouse effect is also lower R32 has got very good thermodynamic features which lead to a really high energy efficiency The units th...

Страница 4: ...ply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard Do not wash the air conditioner with water to avoid electric sho...

Страница 5: ...Do not block air outlet or air inlet It may cause malfunction Do not spill water on the remote controller otherwise the remote controller may be broken When below phenomenon occurs please turn off ai...

Страница 6: ...f the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard The temperature of refrigerant circuit will be high ple...

Страница 7: ...ted by a professional If the length of power connection wire is insufficient please contact the supplier for a new one Avoid extending the wire by yourself For the air conditioner with plug the plug s...

Страница 8: ...Air inlet Filter Air outlet Indoor unit Remote controller Actual product may be different from above graphics please refer to actual products NOTE Display Temp indicator Temp indicator Wi Fi indicato...

Страница 9: ...isconnect the power before cleaning the air conditioner to avoid electric shock Do not wash the air conditioner with water to avoid electric shock Do not use volatile liquid to clean the air condition...

Страница 10: ...ck whether drainage pipe is damaged Checking after use season 1 Disconnect power supply 2 Clean filter and indoor unit s panel Notice for recovery 1 Most of packing materials are recyclable materials...

Страница 11: ...display when operating remote controller Check whether remote controller appears to be damaged If yes replace it Fluorescent lamp in room Take the remote controller close to indoor unit Turn off the...

Страница 12: ...ur source Air conditioner operates normally suddenly Whether there s interference such as thunder wireless devices etc Disconnect power put back power and then turn on the unit again Water flowing noi...

Страница 13: ...professional person L1 PG motor indoor zero crossing detecting circuit malfunction Turn off restart after a few seconds if the code occurs again after a few minutes please contact the professional per...

Страница 14: ...rea is shown on the nameplate or following table 1 4 Leak test is a must after installation Minimum room area m2 Charge amount kg 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 2 4 2 5 floor location...

Страница 15: ...uld be done when it s removed Safety instructions for transportation and storage 1 Please use the flammable gas detector to check before unload and open the container 2 No fire source and smoking 3 Ac...

Страница 16: ...There should be noobstruction near air inlet and air outlet 2 Choose a place where the condensation water can be dispersed easily and won t affect other people 3 Choose a place which is convenient to...

Страница 17: ...5 Be sure to cut off the power supply before proceeding any work related to electricity and safety 6 Do not connect the power before finishing inatallation 7 If the supply cord is damaged it must be r...

Страница 18: ...use pressure rise or compressor rupture resulting in injury 4 During refrigerant recovery make sure that liquid valve and gas valve are fully closed and power is disconnected before detaching the conn...

Страница 19: ...gas around the unit it may cause explosion and other accidents 7 Do not use extension cords for electrical connections If the electric wire is not long enough please contact a local service center au...

Страница 20: ...pipe The position of piping hole should be a little lower than the wall mounted frame shown as below Left Wall 55 70 Right Mark in the middle of it Level meter Rear piping hole Wall Space to the wall...

Страница 21: ...g out the pipe from left or right please cut off the corresponding hole on the bottom case Step 5 Connect the pipe of indoor unit 1 Aim the pipe joint at the corresponding bellmouth 2 Pretightening th...

Страница 22: ...er connection wire to the wiring terminal according to the color tighten the screw and then fix the power connection wirewith wire clip 4 Put wiring cover back and then tighten the screw 5 Close the p...

Страница 23: ...pass through the wall hole 2 Hang the indoor unit on the wall mounting frame 3 Stuff the gap between pipes and wall hole with sealing gum 4 Fix the wall pipe 5 Check if the indoor unit is installed f...

Страница 24: ...water outlet can t be placed in water in order to drain smoothly Slant the drain hose slightly downwards The drain hose can t be curved raised and fiuctuant etc The drain hose can t raise upwards The...

Страница 25: ...supply according to the voltage marked on the nameplate It may cause malfunction or damaging the parts Is electric wiring and pipeline installed correctly It may cause malfunction or damaging the part...

Страница 26: ...rating when first power on and turn on units to ensure the correct installation The steps of test operation is as below A Use remote controller to select cooling mode and set the temperature in 16 C A...

Страница 27: ...C Industria 13 l Pol gono Industrial El Pedregar 08160 Montmel Barcelona Spain Phone 0034 93 390 42 20 Fax 0034 93 390 42 05 info htwspain com www htwspain com...

Отзывы: