background image

LP-314 Rev. 012 Rel. 003 Date 9.27.19

29

NOTE: 

Check with your local gas company to determine if 

combustion condensate disposal is permitted in your area. In the 

state of Massachusetts, condensate must be neutralized before 

entering a drain.

This condensing high efficiency appliance has a condensate removal 

system. Condensate is water vapor derived from combustion 

products, similar to that produced by an automobile when it is 

initially started. It is very important that the condensate line is 

sloped down away from the appliance and to a suitable drain.

If the appliance condensate outlet is lower than the drain, you must 

use a condensate removal pump (kit p/n 554200 available from 

HTP). If required by local authorities, a condensate filter of lime 

crystals, marble, or phosphate chips will neutralize slightly acidic 

condensate. This can be installed in the field and purchased from 

HTP (p/n 7450P-212).

The condensate line must remain unobstructed. If allowed to 

freeze in the line or obstructed in any other manner, condensate 

can exit from the appliance tee, resulting in potential water 

damage to property. When installing a condensate pump, select 

one approved for use with condensing appliances and furnaces. 

The condensate pump should have an overflow switch to prevent 

property damage from spillage. Condensate from the appliance 

will be slightly acidic (pH from 3.2 to 4.5). Install a neutralizing 

filter if required by local codes.

Power to the optional condensate pump is continuous. When the 

appliance is powered off the condensate pump will remain on. It 

is important to remember to turn off the condensate pump when 

powering down the appliance. Failure to do so could result in 

property damage, severe personal injury, or death.

Figure 21 - Condensate Piping

NOTES:

1. Condensate line must be pitched at least ¼” per foot to properly 

drain. If this cannot be done, or a very long length of condensate 

hose is used, increase the condensate line to a minimum of 1” ID and 

place a tee in the line after the condensate neutralizer to properly 

reduce vacuum lock in the drain line.

2. PVC or CPVC pipe should be the only material used for condensate 

line. Steel, brass, copper, and other metals will be subject to 

corrosion or deterioration.

3. A frozen condensate line could result in a blocked vent condition.  

It is very important to protect the condensate line from freezing 

temperatures or any type of blockage. In installations that may 

encounter sustained freezing conditions, the use of heat tape 

is recommended to avoid freezing of the condensate line. It is 

also recommended to bush up the condensate line size to 1” and 

terminate condensate discharge as close to the unit as possible. Longer 

condensate runs are more prone to freezing. Damages due to frozen or 

blocked condensate lines ARE NOT covered by warranty.

4. Support of the condensate line may be necessary to avoid blockage 

of the condensate flow.

Part 7 - Wiring

To avoid electrical shock, turn off all power to the appliance prior to 

opening an electrical box within the unit. Ensure the power remains 

off while any wiring connections are being made. Failure to follow 

these instructions could result in component or product failure, 

serious injury, or death. Such product failure IS NOT covered by 

warranty.
Jumping out control circuits or components WILL VOID product 

warranty and can result in property damage, personal injury, or 

death.

A. Field Wiring

All the wiring connections made to the appliance in the field are done 

on the field connection board located on the right side of the cabinet. 

The cabinet has multiple knockouts available to route field wiring into 

and out of the field connection board. The control provides a pump 

output thermostat and outdoor sensor inputs to operate the central 

heating system.

B. Line Voltage Wiring

1. Connect the normal 

incoming power

 to the terminals marked as 

shown in Figure 22. A line voltage fused disconnect switch may be 

required to be externally mounted and connected according to local 

codes and standards.

2. Connect the 

central heating pump

 as shown in the terminals 

marked CH/DHW PUMP (see Figure 22). The connections shown are 

suitable for a maximum continuous pump draw of 3 amps at 120 

volts. If the pump requires more current or voltage than the 120 volts 

supplied, an external motor starter will be required.

3. Connect the 

NHX pump (if applicable)

 as shown in the terminals 

marked NHX PUMP (see Figure 22). The connections shown are suitable 

for a maximum continuous pump draw of 3 amps at 120 volts. If the 

pump requires more current or voltage than the 120 volts supplied, an 

external motor starter will be required.

NOTE: Wiring must be N.E.C. Class 1. If original wiring as supplied with 

appliance must be replaced, use only TEW 105 

o

C wire or equivalent. 

Appliance must be electrically grounded as required by National 

Electrical Code ANSI/NFPA 70 – latest edition.

C. Low Voltage Wiring

1. Make all low voltage connections to the terminal strip located on the 

field connection board (shown in Figure 22) as outlined below.

2. The 

room thermostat

 should be connected to the terminals marked 

T STAT (shown in Figure 22). Alternately, any dry contact closure across 

these terminals will cause the unit to operate the hydronic heating 

module. NOTE: Caution must be used to ensure neither of the terminals 

becomes connected to ground. Mount the thermostat on an inside 

wall as central as possible to the area being heated, away from drafts 

or heat producing devices such as a television, which could influence 

the ability of the thermostat to measure room temperature accurately. 

NOTE:

 If the thermostat is equipped with a directly connected 

anticipator, the anticipator should be set at .1 amps. If the thermostat 

is connected to other devices, the anticipator should be set to match 

the power requirements of those connected devices. Refer to the 

instruction manuals of the connected devices for further information.

3. The 

outdoor sensor

 must be connected for the unit to operate at 

optimum efficiency. Use a minimum 22 AWG wire for runs of 100 feet 

or less and minimum 18 AWG wire for runs up to 150 feet. Instructions 

are included with the outdoor sensor to correctly mount the sensor 

Part 6 - Condensate Removal

Содержание Versa Hydro PHE130 Series

Страница 1: ...not be held liable for typographical errors in literature NOTE TO CONSUMER PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFERENCE 272 Duchaine Blvd New Bedford MA 02745 www htproducts com LP 314 Rev 012 Rel 003 Date 9 27 19 The surfaces of these products contacted by potable consumable water contain less than 0 25 lead by weight as required by the Safe Drinking Water Act Section 1417 Improper installat...

Страница 2: ...e Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be provided by a qualified installer service agency or the gas supplier Improper installation adjustment alteration service or mainten...

Страница 3: ...d be guided by the instructions furnished with the appliance and by local codes and utility company requirements In the absence of local codes preference should be given to the National Fuel Gas Code ANSI Z223 1 latest version Installations Must Comply With Local state provincial and national codes laws regulations and ordinances The latest version of the National Fuel Gas Code ANSI Z223 1 from Am...

Страница 4: ...6 G Water Temperature Adjustment 6 Part 2 Before You Start 6 A What s in the Box 6 B How the Appliance Operates 6 C Optional Equipment 7 Part 3 Prepare the Appliance 7 A Locating the Appliance 7 B Leveling 8 C Clearances for Service Access 8 D Residential Garage and Closet Installations 8 E Exhaust Vent and Intake Pipe 8 1 Direct Vent of Exhaust and Intake 9 2 Power Venting Indoor Combustion Air i...

Страница 5: ...P Inc appliance with parts not manufactured by HTP Inc WILL INSTANTLY VOID the appliance warranty and could result in property damage personal injury or death High heat sources sources generating heat 100o F 37o C or greater such as stove pipes space heaters etc may damage plastic components of the appliance as well as plastic vent pipe materials Such damages ARE NOT covered by warranty It is reco...

Страница 6: ...These sensors monitor inputs such as outdoor temperature tank temperature and heating module outlet temperature providing data that allows accurate control of the entire system You may choose to use the control s factory default settings or reprogram system parameters to provide design flexibility Hydronic Heating Module The hydronic heating module connects to the storage tank through two dip tube...

Страница 7: ...ponents due to incorrect operating conditions IS NOT covered by product warranty NOTE To prevent condensing in the fan it is recommended to avoid prolonged exposure to temperatures below 45oF This appliance has a condensate disposal system that may freeze if exposed to sustained temperatures below 32 o F Precautions should be taken to protect the condensate trap and drain lines from sustained free...

Страница 8: ...warnings could result in substantial property damage severe personal injury or death NOTE A combustible door or removable panel is acceptable front clearance D Residential Garage and Closet Installations Precautions If the heater is located in a residential garage per ANSI Z223 1 Install the appliance burner and ignition devices a minimum of 18 above the floor of the garage This will ensure the bu...

Страница 9: ...iling the other 6 15cm above the space floor Each opening should have a free area of one square inch per 1 000 BTU hr 22cm2 kW of the total input of all appliances in the space but not less than 100 square inches 645cm2 If the confined space is within a building of tight construction air for combustion must be obtained from the outdoors as outlined in the Venting section of this manual When drawin...

Страница 10: ...stat so the appliance will operate continuously 5 Test for spillage at the draft hood relief opening after 5 minutes of main burner operation Use the flame of a match or candle or smoke from a cigarette 6 After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined return doors windows exhaust fans fireplace dampers and an...

Страница 11: ...ing chlorides in excess of 100 ppm mg L Using chlorinated fresh water should be acceptable as levels are typically less than 5 ppm mg L Do not connect the appliance to directly heat swimming pool or spa water Total Dissolved Solids TDS less than 500 ppm mg L Total dissolved solids are minerals salts metals and charged particles that are dissolved in water The greater the amounts of TDS present the...

Страница 12: ...at the connections on the inlet and outlet are brass or copper Never use dielectric unions or galvanized steel fittings Teflon thread sealant must be used to seal all tank connections An approved ASSE 1017 mixing valve is provided with every appliance and must be installed on the outlet to protect the user from scalding temperatures This valve reduces the point of discharge temperature by mixing t...

Страница 13: ...er Inlet Temperature 120 180oF 49 82oC Min Max ColdWater InletTemperature 39 80oF 4 27oC Max Working Pressure 200 PSI Min Flow Rate 1 GPM Outlet Water Temperature Range 85 130oF 29 54oC Min Temperature Differential Between Hot Supply and Outlet 27oF 15oC Factory Set Locking Ring 120oF Max 1 Allowable Supply Pressure Variation 20 2 Accuracy of Outlet Temperature 3oF 3 4oC Performance CV 1 8 Max Flo...

Страница 14: ...e to any location where freezing could occur No valve may be installed between the relief valve and appliance or in the discharge line Do not plug or place any obstruction in the discharge line Test the operation of the relief valve after filling and pressurizing the system by lifting the lever Make sure the valve discharges freely If the valve fails to operate correctly immediately replace with a...

Страница 15: ...ion and inhibitor level The system should be tested at least once a year or as recommended by the producer of the glycol solution Allowance should be made for the expansion of the glycol solution in the system piping Example 50 by volume glycol solution expands 4 8 in volume for the temperature increase from 32oF to 180oF while water expands 3 with the same temperature rise Listed below are the ba...

Страница 16: ...esign To calculate this you must determine the flow and resistance through the system and heating module The heating module requires 12 GPM at 10 feet of head The system requires 12 GPM at 5 feet of head To select a circulator add the resistance 10 feet of head module 5 feet of head system at 12 GPM This system requires a circulator that operates at a resistance of 15 feet at 12 GPM See examples i...

Страница 17: ...LP 314 Rev 012 Rel 003 Date 9 27 19 17 EXAMPLE At 12 GPM there is approximately 10 ft of head loss Figure 8 Pressure Drop ...

Страница 18: ...BING CODE REQUIRES AN ELECTRONICALLY TIMED CIRCULATOR PUMP TO ACTIVATE EVERY SIX HOURS FOR 60 SECONDS THIS CIRCULATOR IS REQUIRED TO BE BRONZE OR STAINLESS 3 ALL WATER PIPING MUST BE INSULATED 4 YOU MUST INSTALL A VACUUM RELIEF VALVE PER 248 CMR NOTE THIS DRAWING IS MEANTTO DEMONSTRATE SYSTEM PIPING CONCEPT ONLY THE INSTALLER IS RESPONSIBLE FOR ALL EQUIPMENT AND DETAILING REQUIRED BY LOCAL CODES T...

Страница 19: ...QUIRES AN ELECTRONICALLY TIMED CIRCULATOR PUMP TO ACTIVATE EVERY SIX HOURS FOR 60 SECONDS THIS CIRCULATOR IS REQUIRED TO BE BRONZE OR STAINLESS 3 ALL WATER PIPING MUST BE INSULATED 4 YOU MUST INSTALL A VACUUM RELIEF VALVE PER 248 CMR NOTE THIS DRAWING IS MEANT TO DEMONSTRATE SYSTEM PIPING CONCEPT ONLY THE INSTALLER IS RESPONSIBLE FOR ALL EQUIPMENT AND DETAILING REQUIRED BY LOCAL CODES The piping w...

Страница 20: ...appliances Failure to follow these instructions will result in substantial property damage severe personal injury or death NOTE To avoid contamination often contained in indoor air it is best to pipe all intake combustion air directly to the outdoors NOTE Care must be taken to prevent condensate freezing in the exhaust vent pipe system See local state provincial and national codes for best practic...

Страница 21: ... death The exhaust and intake components installed with this appliance must be used for near appliance piping BEFORE transitioning to the approved materials listed above DO NOT REMOVE these installed components Doing so WILL VOID appliance warranty PVC CPVC pipe and fittings of the same diameter are considered interchangeable The use of cellular core PVC ASTM F891 cellular core CPVC or Radel polyp...

Страница 22: ...at may be opened Direct Vent 1 foot 3 feet 91 cm Power Vent 4 ft below or to side of opening 1 ft above opening C Clearance to permanently closed window D Vertical clearance to ventilated soffit located above the terminal within a horizontal distance 2 feet 61 cm from the center line of the terminal E Clearance to unventilated soffit F Clearance to outside corner G Clearance to inside corner H Cle...

Страница 23: ...pace Failure to do so could result in property damage serious injury or death 1 Use only solid PVC CPVC or stainless steel pipe or a Polypropylene vent system approved for use with Category IV appliances ABS pipe material may be used on air inlet piping only 2 Remove all burrs and debris from joints and fittings 3 When using PVC or CPVC pipe all joints must be properly cleaned primed and cemented ...

Страница 24: ...e pipe in a parking area where machinery may damage the pipe DO NOT vent near soffit vents crawl space vents or other areas where condensate or vapor could create a nuisance or hazard or cause property damage DO NOT vent where condensate vapor could cause damage or could be detrimental to the operation of regulators relief valve or other equipment In the Commonwealth of Massachusetts and as Requir...

Страница 25: ...ent and detailing required by local codes All vent pipes must be glued properly supported and the exhaust pitched a minimum of 1 4 per foot back to the appliance to allow drainage of condensate When placing support brackets on vent piping the first bracket must be within 1 foot of the appliance and the balance of 4 foot intervals on the vent pipe Venting must be readily accessible for visual inspe...

Страница 26: ... Concentric Venting Through an Existing System and Venting as a Chase Vent Air Inlet Size Minimum Existing Vent Chase Size 2 4 3 5 4 7 Table 10 Minimum Existing Vent Chase Sizing NOTES A For every 1 of overhang the exhaust vent must be located 1 vertical below overhang overhang means top of building structure and not two adjacent walls corner of building B Typical installations require 12 minimum ...

Страница 27: ... 13 LP 325 NN INTAKE EXHAUST 24 SEAL EXISTING VENT CAP SEAL Exhaust Intake Chase Venting through an Existing System 3 Figure 18 1 2 Concentric Venting Through an Existing System 3 Chase Venting Through an Existing System NOTE These drawings are meant to demonstrate system venting only The installer is responsible for all equipment and detailing required by local codes 3 Power Venting Indoor Combus...

Страница 28: ...ace Appliance Near Dryer ROOM OPENING ROOM OPENING 6 6 EXHAUST LP 325 S 09 29 11 Boiler Water Heater or Appliance Indoor Combustion Air Single Pipe EXHAUST UPPER AIR DUCT LOWER AIR DUCT LP 325 T 8 5 2010 Boiler Water Heater or Appliance Outdoor Combustion Air Single Pipe Figure 20 Indoor and Outdoor Combustion Air Single Pipe ...

Страница 29: ...ning an electrical box within the unit Ensure the power remains off while any wiring connections are being made Failure to follow these instructions could result in component or product failure serious injury or death Such product failure IS NOT covered by warranty Jumping out control circuits or components WILL VOID product warranty and can result in property damage personal injury or death A Fie...

Страница 30: ...its maximum of 10 volts the appliance will increase in set point temperature See Part 10 for details on the setting of Function 16 NOTE During 0 10V operation the minimum tank temperature set point Function 9 default 68oF will be at the activation input of 1 5 volts The maximum tank temperature set point value will be at the input voltage of 10 volts The maximum tank temperature set point can be c...

Страница 31: ...LP 314 Rev 012 Rel 003 Date 9 27 19 31 Figure 22 Customer Connection Board F Customer Connection Board ...

Страница 32: ...INTERNAL 6 3 AMP FUSE t SUPPLY RETURN X1 1 X1 11 X1 2 30v FAN 0v FAN BIC926 BIC926 30v FAN J5 SAFETY SWITCH X4 4 J 4 J6 1 J6 2 J6 3 X1 15 X1 5 X1 3 J9 8 J9 7 X1 13 SENSOR TO TANK X1 8 X1 18 X1 19 X1 9 X 1 X 4 PUMP MODULE HYDRONIC 0 10V RL 1 BLACK RED RED J20 1 YEL YEL J20 6 YEL YEL BLUE BLUE J20 7 BLUE BLUE J20 2 RED RED J20 3 J20 8 J20 9 RED J20 4 RED RED J20 10 RED PINK PINK RED RED J9 4 RED RED...

Страница 33: ...LP 314 Rev 012 Rel 003 Date 9 27 19 33 Figure 24 Control Board Wiring ...

Страница 34: ... natural gas applications where there is a potential for an explosive mixture of fuel gas to accumulate The installation of these detectors should be made in accordance with the detector manufacturer s recommendations and or local laws Failure to install fuel gas detectors in these applications could result in fire explosion property damage severe personal injury or death A Gas Pipe Sizing Tables ...

Страница 35: ... supply This adjustment could affect CO levels Make sure the levels correspond to the chart in combustion setting THROTTLE ADJUSTER NOTE If for any reason the throttle needs to be adjusted it is very important that a OFFSET ADJUSTMENT CAUTION Do not remove or attempt to make any adjustments to this screw without a COMBUSTION PRESSURE TAP OUTLET Figure 26 Gas Valve 5 The National Fuel Gas Code NFPA...

Страница 36: ...sideoftheappliance is fully purged of air To purge the tank turn on the cold water feed and open a faucet at the highest point of the system Observe filling of the tank and inspect for any leaks in the system which may occur and need to be repaired Shut off faucet once all evidence of air is purged from the water stream B Fill and Purge Hydronic Heating Loop 1 Local codes may require back flow pre...

Страница 37: ...ined based on program settings 6 After you have entered and stored the Central Heating value press once The second screen adjusts the heating system Heating Delta T value The factory default is 20oF 7 After you have entered and stored the Heating Delta T value press once The third screen adjusts the DHW Set Point Adjust the value to the desired Domestic Hot Water temperature The factory default is...

Страница 38: ...he system is ready to run Adjust thermostats to the desired value Total System Control will now modulate and control the system 68 F 5 F 120 F 160 F 140 F WARM WEATHER SHUT DOWN FUNCTION 4 HEATING SYSTEM DELTA T FUNCTION 6 FUNCTION 5 FUNCTION 7 FUNCTION 8 DESIRED DHW OUTLET TEMPERATURE HYDRONIC HEATING SUPPLY TEMPERATURE TANK TEMPERATURE MAX TANK TEMPERATURE FUNCTION 2 APPLIANCE TEMPERATURE PERFOR...

Страница 39: ... for further setup and operation details BURNER RUN OFFSET 5 oF Adjusts the offset from the current target tank temperature where the control will begin heating water Range 1 to 18oF Factory default 5oF TEMP DISPLAY C OR F oF Adjusts the temperature measurement in F Fahrenheit to C Celsius Default is Fahrenheit Table 14 Appliance Setting Program Navigation Clock Settings NOTE The clock will reset ...

Страница 40: ...s open or shorted NOTE This error does not stop the appliance from running Factory default ON Range ON OFF PHOEN ON Function 13 Error System Sensor ERROR SYSTEM SENS ON 13 Sets the control to display an error message if the system sensor is open or shorted NOTE This error does not stop the appliance from running Factory default ON Range ON OFF NOTE Press ENTER to store system parameters Function 1...

Страница 41: ...nditions and Total System Control settings Press v once FLAME 0 0uA FAN SPEED 3497 RPM This screen displays appliance flame current on the top line The second line displays appliance fan speed Press v once POWER ON 0h INPUT 0kBTU The top line indicates the amount of hours the appliance has been powered in its lifetime The bottom line displays how much energy input in thousand BTU from the burner i...

Страница 42: ...P ON 4 49P Combustion Settings on All Models Fan Speed Natural Gas NG Propane LP Low Ignition High Low Ignition High Carbon Monoxide CO PPM 1 10 2 15 2 20 1 10 2 15 2 20 Carbon Dioxide CO2 8 10 8 1 2 10 1 2 9 11 Table 18 Combustion Settings All Models Fan Speeds BTU Ignition Min Max 130 000 3000 2000 7300 199 000 2100 9100 Table 19 Fan Speeds NOTE The appliance will automatically exit Test Mode af...

Страница 43: ... outdoor reset feature and run at the programmed temperature The bottom line indicates the status of the pump Inspect wiring from outside sensor for damage or shorted connections and repair as necessary Measure resistance of the outdoor sensor and compare to resistance chart If not within range on chart shorted or open replace sensor CH SENSOR FAIL PUMP ON E07 This indicates that one or both of th...

Страница 44: ...voltage sensor wiringforshortstogroundandrepairasnecessary Ifmessage is still present disconnect the UL 353 low water cutoff to see if message clears Replace faulty part Check low voltage wire harness in appliance for shorts to ground 5 Remove the 20 pin Molex from the ECS board If the message clears examine the wiring to the heating module and fan for shorts or grounds and repair as necessary 6 I...

Страница 45: ...he bottom line 1 Check the electrical connection to the thermistor on the outlet manifold Verify 5VDC by checking in Molex connector If not 5 VDC check harness If harness is OK replace control NOTE Verify thermistor values by referencing the resistance table in this manual 2 Replace thermistor if necessary BOT TEMP HIGH PUMP ON F06 F06 indicates the bottom temperature of the tank is excessive If t...

Страница 46: ...ds The red fault light and flashing LOCKOUT on the display indicate a serious safety issue The unit will not restart until the technician repairs and resets the unit During this lockout fault the pump will be on as indicated on the second line of the display 1 Check the combustion air fan wiring 2 Measure the DC voltage from the red fan wire to ground while it is connected to the fan It should be ...

Страница 47: ...15 202 786 212 667 Table 22 Sensor Temperature Resistance Part 13 Shutdown A Shutdown Procedure If the burner is not operating disconnect the electrical supply If the burner is operating lower the set point value to 70oF and wait fortheburnertoshutoff Continuetowaitforthecombustionblower to stop so all latent combustion gases are purged from the system This should take a maximum of 40 to 90 second...

Страница 48: ...nations been installed at least one foot above exterior grade and one foot above normal snow accumulation level Is vent piping properly supported Has vent piping been checked for leaks Has the exhaust vent line been pitched back to the appliance at a rate of 1 4 per foot Have the exhaust vent and intake pipes been properly installed to the appliance Install Condensate Piping Tubing and Components ...

Страница 49: ...merged Attempting to operate an appliance that has been submerged could create numerous harmful conditions such as a potential gas leakage causing a fire and or explosion or the release of mold bacteria or other harmful particulates into the air Operating a previously submerged appliance could result in property damage severe personal injury or death NOTE Appliancedamageduetofloodorsubmersioniscon...

Страница 50: ...mbers cloth to remove oxides Flame Probe Check ionization uA see Status Menu Record high fire and low fire Clean probe with plumbers cloth to remove oxides Condensate 1st Year 2nd Year 3rd Year 4th Year Neutralizer Check condensate neutralizer Replace if necessary Condensate Pipe Disconnect condensate pipe Clean out dirt Fill with water to level of outlet and reinstall NOTE Verify the flow of cond...

Страница 51: ...1 1 4 5 1 P 0 5 2 7 B R A B E S O H S S 2 1 4 0 1 P 0 0 1 7 T E L N I R I A T U N G N I L P U O C 3 1 4 6 2 P 0 0 1 7 T E N I B A C C I T S A L P L A G 0 8 5 5 4 1 5 6 2 P 0 0 1 7 T E N I B A C C I T S A L P L A G 9 1 1 15 CONTROL BOARD DISPLAY w MEMBRANE BOARD HOUSING CABLE 7100P 266 7 8 0 P 0 0 5 7 H C T I W S R E W O P 6 1 6 5 1 P 0 0 1 7 E T A L P K C A B E L U D O M C I N O R D Y H L A G 0 8 ...

Страница 52: ...art Numbers 130kBTU 55 Gal 7100P 1140 Solar 130kBTU 80 Gal 7100P 1146 130kBTU 80 Gal 7100P 1141 Solar 130kBTU 119 Gal 7100P 1147 130kBTU 119 Gal 7100P 1142 Solar 199kBTU 80 Gal 7100P 1148 199kBTU 55 Gal 7100P 1143 Solar 199kBTU 119 Gal 7100P 1149 199kBTU 80 Gal 7100P 1144 199kBTU 119 Gal 7100P 1145 Table 25 Control Board Replacement Part Numbers ...

Страница 53: ...ASS 7100P 105 12 SIGHT GLASS w GASKET 7100P 022 13 1 4 20 BRASS NUTS 1 4 LOCK WASHERS 7100P 268 14 AIR CHANNEL 7700P 003 15 GASKET BLOWER TO AIR CHANNEL 7500P 075 16 COMBUSTION BLOWER 7100P 330 17 SCREWS 10 32 X 1 2 7700P 094 18 ADAPTER PLATE 7250P 644 19 FLAT HEAD SCREW ADAPTER PLATE 7100P 045 20 AIR INTAKE ADAPTER BLOWER SIDE 7500P 185 21 SWIRL PLATE BLACK 130K BTU 7100P 042 SWIRL PLATE WHITE 19...

Страница 54: ...iance H This warranty extends only to Versa Hydro Combined Appliances utilized in heating applications that have been properly installed based upon manufacturer s installation instructions I It is expressly agreed between HTP and the Owner that repair replacement or refund are the exclusive remedies of the Owner OWNER RESPONSIBILITIES The Owner or Qualified Installer Service Technician must 1 Have...

Страница 55: ...ll be reviewed by HTP within three 3 business days If additional information is required and requested by the HTP Claims Departmentyouwillhavethirty 30 daystoprovideit Whenallrequested information is provided HTP will respond within three 3 business days The claim will be automatically closed if requested information is not provided within thirty 30 days Claims will not be reopened without HTP War...

Страница 56: ...LP 314 Rev 012 Rel 003 Date 9 27 19 56 Maintenance Notes ...

Страница 57: ...tallation Installation Address Product Name Serial Number s Comments Installer s Code Name Installers Phone Number Signed by Installer Signed by Customer Installation Notes IMPORTANT Customer Please only sign after the qualified installer service technician has fully reviewed the installation safety proper operation and maintenance of the system If the system has any problems please call the quali...

Отзывы: