lp-441 Rev. 002 Rel. 008 Date 8.23.18

35

Resistance Table for Supply Temperature Sensor

High / Low Temp Sensor Temp. (

o

F)

Resistance (Ohms)

32

32550

41

25340

50

19870

59

15700

68

12490

77

10000

86

8059

95

6535

104

5330

113

4372

122

3605

131

2989

140

2490

149

2084

158

1753

167

1481

176

1256

185

1070

194

915

202

786

212

667

Table 17 - Supply Temperature Resistance Sensor

B. Test Mode

Test Mode is enabled by pressing 

 or 

 together for 5 seconds. 

In this mode the water heater operates without modulation, and the 

combustion system initially runs at the maximum fan speed. The 

SERVICE symbol is displayed on the LCD when Test Mode is active. 

Test Mode can be used to incrementally increase and decrease 

fan speed to test the combustion system. See the tables below for 

Combustion Settings and Fan Speeds.
1. Use the 

 or 

 buttons to decrease or increase the fan 

speed in increments of 50 rpm.
2. Press 

 to advance directly to the maximum fan speed.

3. Press 

 to go directly to the minimum fan speed.

4. Range between minimum and maximum fan speed is taken as an 

absolute power value (0 - 100%).

5. During Test Mode, the LCD flame symbols are enabled as follows:

Flame ON and power < 30% -   - 1/3 flame symbol

Flame ON and power > 30%  and <75% -   - 2/3 flame symbol

Flame ON and power > 75% -   - full flame symbol

6. Burner ON and OFF conditions are:

Burner ON: UPPER temperature < 185

o

C

Burner OFF: UPPER temperature ≥ 194

o

C

7. Test Mode can be enabled for a maximum of 15 minutes.

8. Test Mode can be disabled by pressing 

.

Combustion Settings on All Models

Fan Speed

Natural Gas (NG)

Propane (LP)

Low Ignition High Low Ignition High

Carbon Monoxide 

(CO) PPM

1-10

2-15

2-20 1-10

2-15

2-20

Carbon Dioxide 

(CO2) %

8-10

8 1/2- 10 1/2

9-11

Table 18 - Combustion Settings - All Models

Fan Speeds

Fuel

Ignition

Min

Max

Natural Gas

5000

2150

6300

Propane

3800

2100

Table 19 - Fan Speeds

4. Adjust the temperature set point of the heater to the desired level. 

The factory default setting is 120

o

F. If changes are necessary, follow 

“Basic Control Functions” in this manual.

5. If the water heater fails to start, refer to the Troubleshooting 

section in the back of this manual.

C. Maintenance

The control system requires no periodic maintenance under normal 

conditions. However, in unusually dirty or dusty conditions, periodic 

vacuuming of the cover to maintain visibility of the display and 

indicators is recommended. In dirty environments, such as construction 

sites, care must be taken to keep the water heater burner cover in place 

and drywall or saw dust away from water heater.

In unusually dirty or dusty conditions care must be taken to keep 

water heater burner door in place. Failure to do so VOIDS warranty. 

It is very important that the combustion system be set within the 

recommended CO measurements listed below. Visually looking 

at the burner does not determine combustion quality. Failure to 

measure combustion with a calibrated Combustion Analyzer and 

set the throttle within the recommended CO measurements could 

result in property damage, severe personal injury, or death.

Содержание Phoenix 7100P-124

Страница 1: ...not be held liable for typographical errors in literature NOTE TO CONSUMER PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFERENCE 272 Duchaine Blvd New Bedford MA 02745 www htproducts com lp 441 Rev 002 R...

Страница 2: ...Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas...

Страница 3: ...mustbeinstalledbyqualifiedandlicensedpersonnel The installer should be guided by the instructions furnished with the water heater and by local codes and utility company requirements In the absence of...

Страница 4: ...the Box 6 B How the Heater Operates 6 C Optional Equipment 6 Part 3 Prepare the Water Heater 6 A Locating the Water Heater 7 B Leveling 7 C Clearances for Service Access 8 D Residential Garage and Cl...

Страница 5: ...table water ONLY Using this water heater to heat non potable fluid WILL VOID product warranty and could result in property damage personal injury or death Do not use this water heater for anything oth...

Страница 6: ...system monitors water temperature and adjusts fan speed to regulate the heater s energy output This allows the unit to deliver the required amount of heated energy and nothing more Burner Constructed...

Страница 7: ...ontrol system components must be protected from dripping water during operation and service 5 If the heater is to replace an existing heater check for and correct any existing system problems such as...

Страница 8: ...nt termination assembly Doing so could result in severe personal injury or death Do not attempt to vent this water heater by any means other than those described in this manual Doing so will void the...

Страница 9: ...space such space should be provided with two permanent openings one located 6 15cm below the space ceiling the other 6 15cm above the space floor Each opening should have a free area of one square inc...

Страница 10: ...corrosive chemicals or elements that can damage the heat exchanger Potable water is defined as drinkable water supplied from utility or well water in compliance with EPA secondary maximum contaminant...

Страница 11: ...quired by ANSI Part 4 Piping Failure to follow the instructions in this section WILL VOID the warranty and may result in property damage severe personal injury or death DO NOT pipe this water heater w...

Страница 12: ...The expansion tank must be located as shown in Applications this manual or following recognized design methods See expansion tank manufacturer s instructions for details Use a backflow preventer speci...

Страница 13: ...temperature as low as possible Feel water before bathing or showering If thermostatic valves are required use devices specifically designed for such purpose Install these devices in accordancewithins...

Страница 14: ...all equipment and detailing required by local codes In Massachusetts you must install a vacuum relief valve per 248 CMR 6 Mixing valve application is optional but recommended to help prevent scalding...

Страница 15: ...thout water will result in dry firing NOTES FOR AIR HANDLER APPLICATION 1 MASSACHUSETTS STATE PLUMBING CODE REQUIRES A DISTANCE NO GREATER THAN 50 FEET FROM THE WATER HEATER TO THE FAN COIL IN THE AIR...

Страница 16: ...state provincial and national codes for best practices to prevent condensate freezing in the exhaust vent pipe system Improper seating of vent pipe gaskets can cause eventual gasket failure and exhaus...

Страница 17: ...p terminations clear could result in property damage severe personal injury or death The exhaust and intake components installed with this water heater must be used for near water heater piping BEFORE...

Страница 18: ...t may be opened Direct Vent 1 foot 3 feet 91 cm Power Vent 4 ft below or to side of opening 1 ft above opening C Clearance to permanently closed window D Vertical clearance to ventilated soffit locate...

Страница 19: ...piping may be used on air inlet piping only 2 Remove all burrs and debris from joints and fittings 3 When using PVC or CPVC pipe all joints must be properly cleaned primed and cemented Use only cemen...

Страница 20: ...y three feet for concealed piping b At all changes of direction c On each side of a penetration through a partition wall or ceiling and d The labels shall be black lettering that i Indicates that the...

Страница 21: ...ing support brackets on vent piping the first bracket must be within 1 foot of the water heater and the balance of 4 foot intervals on the vent pipe Venting must be readily accessible for visual inspe...

Страница 22: ...IDE VIEW LP 325 PP EXHAUST AIR INTAKE F E D C EXHAUST AIR INTAKE B Figure 10 Horizontal Snorkel Venting UNBALANCED VENTING WITH TEE INTAKE AND COUPLING EXHAUST All vent pipes must be glued properly su...

Страница 23: ...Concentric Vent Kit installation manual LP 166 for further information on venting with the optional concentric vent kits Concentric venting through an existing system must run vertically through the...

Страница 24: ...idered part of the space Confined space is space with volume less than 50 cubic feet per 1 000 Btu hour 4 8 cubic meters per kW of the total input rating of all fuel burning appliances installed in th...

Страница 25: ...rom 3 2 to 4 5 Install a neutralizing filter if required by local codes Power to the optional condensate pump is continuous When the water heater is powered off the condensate pump will remain on It i...

Страница 26: ...lp 441 Rev 002 Rel 008 Date 8 23 18 26 1 2 3 4 Figure 16 Removing and Installing the Condensate Neutralizer Water Heaters Manufactured Prior to 9 27 17 ONLY...

Страница 27: ...ns are included with the outdoor sensor to correctly mount the sensor on the exterior surface of the building It is preferable to mount the sensor on the north side in an area that will not be affecte...

Страница 28: ...ing plate LP for liquefied petroleum propane gas or Nat for natural or city gas All gas connections must be approved by the local gas supplier or utility in addition to the governing authority prior t...

Страница 29: ...being installed If there are additional gas appliances on the main supply line size the supply line for the maximum total COMBINED BTU Hr draw of the appliances This will ensure the supply line is siz...

Страница 30: ...s individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of the system at pressures greater than psi 3 5 kPa 2 The water heater must be isolated fr...

Страница 31: ...t in increments of two degrees After choosing the setpoint wait five seconds The screen will return to normal operation and the setpoint will be stored 70 160 120 Outdoor Reset Curve Enabling Outdoor...

Страница 32: ...ume water heater operation 3 Putting the Water Heater in ECO Mode Press to put the water heater in ECO Mode Press to resume normal operation 4 Changing User Setpoint Press either or once to change the...

Страница 33: ...mum tank temperature for reset curve 70 160 140 P10 Warm Weather Shutdown Temperature o C o F Outdoor temperatures greater than this value return the tank target temperature to the User Setpoint 50 10...

Страница 34: ...een cleared Press at any History Mode screens to return to the upper level menu Part 10 Start Up Procedure FOR YOUR OWN SAFETY READ BEFORE OPERATING 1 This water heater does not have a pilot It is equ...

Страница 35: ...maximum of 15 minutes 8 Test Mode can be disabled by pressing Combustion Settings on All Models Fan Speed Natural Gas NG Propane LP Low Ignition High Low Ignition High Carbon Monoxide CO PPM 1 10 2 1...

Страница 36: ...result in property damage serious personal injury or death Such damages ARE NOT covered by water heater warranty Part 12 Troubleshooting A Error Code An error code may occur during installation of the...

Страница 37: ...the sensor is 40o F 122o F 2 Check the Outdoor Temperature Sensor Ensure it is properly wired and connected and that there are no breaks cuts or other visible issues with the sensor wire 3 Use an ohmm...

Страница 38: ...ault code occurs again reset the water heater and 3 When water heater attempts to fire check voltage at the gas valve connector If there is voltage but no gas pressure on the outlet side of the valve...

Страница 39: ...erve water heater operation If fault code occurs again 3 Check the Dual Temperature Sensor Ensure it is properly wired to the control and that there are no breaks cuts or other visible issues with the...

Страница 40: ...ons been installed at least one foot above exterior grade and one foot above normal snow accumulation level Is vent piping properly supported Has vent piping been checked for leaks Has the exhaust ven...

Страница 41: ...er that has not been used for a long period of time generally two weeks or more When opening a hot water faucet in a system that has been out of use for a time keep all ignition sources electrical app...

Страница 42: ...ctrode Clean Set gap at 1 4 Clean probe with plumbers cloth to remove oxides Combination Ignitor and Flame Probe Check ionization in uA i04 in the Inquiry Mode menu Record high fire and low fire Clean...

Страница 43: ...T P A D A 4 8 6 0 P 0 0 7 7 S P M A L C w E S O H E T A S N E D N O C 5 4 4 0 P 0 0 1 7 B R A B X E L A M T P N 2 1 G N I T T I F 6 2 0 0 P 0 0 7 7 2 1 T U N K C O L 7 7 7 0 P 0 0 7 7 2 1 X 2 1 R E T...

Страница 44: ...0P 004 27 CONDENSATE HOSE w CLAMPS 7700P 068 28 FITTING 1 2 NPT MALE X BARB 7100P 044 29 LOCKNUT 1 2 7700P 002 30 ADAPTER 1 2 X 1 2 7700P 077 31 FLUE TEMPERATURE SENSOR 7450P 026 32 PRESSURE SWITCH 77...

Страница 45: ...of the water heater and NOT the date of installation of the water heater F This warranty extends only to water heaters utilized in water heating applications that have been properly installed by quali...

Страница 46: ...whenever possible d A picture of the piping near the product e For gas fired products a picture of the venting including how it exits the building All claims will be reviewed by HTP within three 3 bu...

Страница 47: ...lp 441 Rev 002 Rel 008 Date 8 23 18 47 Maintenance Notes...

Страница 48: ...allation Installation Address Product Name Serial Number s Comments Installer s Code Name Installers Phone Number Signed by Installer Signed by Customer Installation Notes IMPORTANT Customer Please on...

Отзывы: