13
ADDRESS
DESCRIPTION
DEFAULT
UNIT
MIN
MAX
RESOLUTION
30018
Outlet temp 1
0
Deg F
-76
266
0, 1
30019
Inlet temp 1
0
Deg F
-76
266
0, 1
30020
Flue temp 1
0
Deg F
-76
266
0, 1
30021
Firing rate 1 / Appliance 1 pump
speed / Pump 4
0
%
0
100
0, 1
30022
OUTPUT
0
%
0
100
1
30023
Appliance 1 status code
0
NA
0
65535
30024
Appliance 1 blocking code
0
NA
0
65535
30025
Appliance 1 lockout code
0
NA
0
65535
30026
Appliance 2 outlet temperature
0
Deg F
-76
266
0, 1
30027
Appliance 2 firing rate
0
%
0
100
1
30028
Appliance 2 status
0
NA
0
65535
30029
Appliance 2 lockout code
0
NA
0
65535
30030
Appliance 3 supply temperature
0
Deg F
-76
266
0, 1
30031
Appliance 3 firing rate
0
%
0
100
1
30032
Appliance 3 status
0
NA
0
65535
30033
Appliance 3 lockout code
0
NA
0
65535
30034
Appliance 4 supply temperature
0
Deg F
-76
266
0, 1
30035
Appliance 4 firing rate
0
%
0
100
1
30036
Appliance 4 status
0
NA
0
65535
30037
Appliance 4 lockout code
0
NA
0
65535
30038
Appliance 5 supply temperature
0
Deg F
-76
266
0, 1
30039
Appliance 5 firing rate
0
%
0
100
1
30040
Appliance 5 status
0
NA
0
65535
30041
Appliance 5 lockout code
0
NA
0
65535
30042
Appliance 6 supply temperature
0
Deg F
-76
266
0, 1
30043
Appliance 6 firing rate
0
%
0
100
1
30044
Appliance 6 status
0
NA
0
65535
30045
Appliance 6 lockout code
NA
0
65535
30046
Appliance 7 supply temperature
0
Deg F
-76
266
0, 1
30047
Appliance 7 firing rate
0
%
0
100
1
30048
Appliance 7 status
0
NA
0
65535
30049
Appliance 7 lockout code
0
NA
0
65535
30050
Discrete inputs 49 - 64
0
NA
0
65535
30051
NTC 6 temperature
0
Deg F
-76
266
0, 1
30052
NTC 7 temperature
0
Deg F
-76
266
0, 1
30053
Solar Panel temperature
0
Deg F
-76
266
0, 1
30054
Solar flow
0
LPM
0
100
0, 1
30055
Solar temp
0
Deg F
14
248
0, 1
HOLDING REGISTERS
40001
Configuration
See below
40002
Coils
40003
0
– 10 volt / rate / set point CMD
V
0
248
0, 1
40004
Tank set point
Deg F
0
10
0, 1
40005
Tank temperature
Deg F
-76
212
0, 1
40006
Outdoor temperature
Deg F
-76
266
0, 1
40007
System supply temperature
Deg F
-76
266
0, 1
40008
System return temperature
Deg F
266
40009
I4 for direct mode
20
Deg F
0
36
0, 1
40010
CH post purge
0
Seconds
0
255
1
40011
DH post purge
0
Seconds
0
255
1
40012
Solar Pump speed
0
%
0
100
0, 1
40014
Extra 0
– 10 volt output
0
%
0
100
0, 1
Table 10
– Modbus memory map
NOTE:
Use Blocking Codes and Lockout Codes to interpret remote boiler operating conditions.
C. BLOCKING CODES
BLOCKING CODES (INPUT REGISTERS 30015 AND 30024)
NUMBER
DEFINITION
0
None
11
water pressure low