6.2.3. “HARM"
mode
By selecting the HARM mode one of the screens below will be displayed according to the
settings made as per paragraph 5.2. The screens show the harmonics (see paragraph
16.2) of the phase currents.
Example of screen in single-
phase mode
Example of screen in “3-wire”
or “4-wire” three-phase mode
The symbols used are described in Tab. 2. For eventual messages displayed see chapter
14. The displayed histograms represent the harmonic content of the current under test.
The value of the first harmonic h01 (primary at 50Hz) is not represented in scale along with
the other harmonics in order to maximize the display of the latter. In case both voltage and
current are connected to the instrument inputs, eventual negative values (therefore
represented under the horizontal axis), indicate that such current harmonics are
“generated” by the load. Following keys are enabled:
•
F3
,
F4
:
to move the cursor of the selected harmonic leftwards and rightwards
respectively. At the same time the values relevant to the order no. of
the selected harmonic and to the corresponding absolute and relative
values (calculated on the basis of the fundamental) are updated.
•
F1
(only for three-phase mode): to display the values of the harmonics of
the other voltages available. The voltage displayed is indicated above
the F3 key.
•
F2
:
to display the page of the harmonics h01
÷
h24 (
h24
symbol) or that of
the harmonics h25
÷
h49 (
h49
symbol).
•
ESC
:
to return back to METER mode (see paragraph 6.2.2)
•
SAVE
:
to store in the instrument memory a record of “Smp” type (see
paragraph 5.4) and the instantaneous values of voltage and current
present on the instrument inputs. This function is disabled during a
recording.
•
ENTER/HOLD
: to enable/disable the HOLD function (updating interruption) of the
displayed data. All the previous functions remain however available.
When the HOLD function is enabled, the word
HOLD
is displayed.
When this function is enabled it’s not possible to record or take an
energy measurement. This function is disabled during a recording or
an energy measurement.
•
MENU
:
to enter the
MENU
mode and change the instrument settings (see
paragraph 5.2 and 5.3). It’s not possible to enter the configuration
MENU during a recording or an energy measurement.
•
START/STOP
: to record
selected parameters
according to the instrument’s settings
(see chapter 7).
27.09.00 17:35:12
I1 = 230.2 A
h03 = 10.2 A
h03 = 4.3 %
ThdI = 11.0 %
h49
←
→
27.09.00 17:35:12
I1 = 230.2 A
h03 = 10.2 A
h03 = 4.3 %
ThdI = 11.0 %
ChgP
h49
←
→