background image

August-2015 

Page 7 

 

 

3.2.2.

 

Dry contacts 

HST-HP201-2 contains 3 dry contact remote inputs. Triggering of any input is done by 

connecting 0V terminal beside input terminal with the selected input. Input signal is latched 
until fire reset. After fire reset if remote input is still connected to 0V terminal, programmed 
action will be active again. Triggering any input is available under access level 1 so care must 
be taken in programming any of remote inputs. By default all inputs are not programmed so 
there will be no effect if connected to 0V terminal. Inputs can be programmed from panel 
configuration menus or from computer software. 

 

3.2.3.

 

Sounders 

HST-HP201-2 contains 2 class B monitored conventional sounder circuits used to 

connect different conventional sound strobe or bell devices. Each circuit is fused @1A.10KΩ 
end of line resistor must be connected for open & short circuit faults detection. By default 
both sounder circuits trigger on any fire or manual evacuate conditions. Different 
configurations can be done from panel configuration menus or from computer software. 

Содержание HST-HP201-2

Страница 1: ...HLogic Security Technology HST HP201 2 Addressable Fire Alarm Control Panel Product Manual August 2015 UMPL 101 R 1 00 ...

Страница 2: ...key 8 3 3 4 Fire function keys 9 3 3 5 General function keys 9 3 3 6 Test key 9 3 3 7 Enable key 10 3 4 Front panel indicators 10 3 4 1 LCD 10 3 4 2 LEDs 10 3 4 3 Buzzer 11 4 Installation 12 5 Panel operation 13 5 1 Access levels 14 5 2 Panel states 15 5 3 LCD icons 16 5 4 Working with main screen 17 6 Programming 21 6 1 Onboard programming 22 6 1 1 Sub menu items 22 6 1 1 1 Menu1 System configura...

Страница 3: ...August 2015 Page 3 7 Appendixes 44 7 1 Appendix A Panel Default Values 44 ...

Страница 4: ... buzzer silence alarm resound alarm reset 1 onboard fixed evacuate key 2 onboard programmable keys Full navigation keys full numeric keypad 16 onboard functional LED indicators for different panel states 250 zones with 32 onboard zonal LED indicators 4000 event log records Large graphical display 240 X 128 pixels 1 RS 232 interface for PC panel con_guration tool Lock key for con_guration update ac...

Страница 5: ...inside the main terminal block which holds 230VAC input terminal located at the upper right part of the panel Also panel has terminals to connect 2 X 12V 7Ah sealed lead acid batteries for panel backup power in case of failure of main input power Main panel board has a charging circuit to charge the batteries Charging circuit is automatically disconnected as soon as batteries are fully charged to ...

Страница 6: ... A detection loop circuits Each loop can hold up to 250 addressable loop devices Loop output devices Sounders Modules should not exceed 64 devices per loop and remaining could be input devices Detectors Call points Loop communication protocol is HST protocol Loop resistance should not exceed 90Ω for reliable operation Loops are monitored for open short circuit faults and communication errors Each ...

Страница 7: ... of remote inputs By default all inputs are not programmed so there will be no effect if connected to 0V terminal Inputs can be programmed from panel configuration menus or from computer software 3 2 3 Sounders HST HP201 2 contains 2 class B monitored conventional sounder circuits used to connect different conventional sound strobe or bell devices Each circuit is fused 1A 10KΩ end of line resistor...

Страница 8: ... via standard straight DB9 cable Panel connector is located lower left side of the panel Serial connection settings are fixed with the following values 9600 BPS baud rate 8 data bits no parity bits 1 stop bit and no handshaking 3 3 Front panel controls 3 3 1 Numeric keys HST HP201 2 contains full numeric keypad used for general panel operation and panel programming 3 3 2 Navigation keys HST HP201 ...

Страница 9: ...ault condition All onboard and loop modules will return to its default state In case that condition which caused the fire or fault is still active panel will change its state again according to the active event Evacuate key Used to perform manual evacuate action 3 3 5 General function keys HST HP201 2 contains 2 onboard general function keys which can be programmed independently to perform one of ...

Страница 10: ...ckup batteries Fire Indicates the presence of at least one fire condition Evacuate Indicates the presence of at least one manual evacuate condition Pre Alarm Indicates the presence of at least one pre alarm condition Silence Buzzer Indicates that Silence Buzzer key is pressed after fire or fault condition It will be turned off in case of another fire or fault condition is triggered Silence Alarm I...

Страница 11: ... communication fault It will be turned off when fault restored Sounder Fault Indicates the presence of at least one onboard sounder circuit open circuit fault or short circuit fault It will be turned off when fault restored Test Indicates that panel is under test condition MCU Fault Indicates the presence of panel processor unrecognized behavior Zone 1 32 Each LED Indicates the presence of at leas...

Страница 12: ... upper side of the main board Remove power socket at the right down side of the board Remove the left side cable which connects the main board to the display board by opening the lock parts of the socket and unplug the cable Then remove the 6 screws which mount the main board to the case There is one at each side of the board and one at the top middle and one at the bottom center Mark and drill th...

Страница 13: ...ay all errors after scan phase is finished If there is any error in communication with the loop loop scan will be aborted and loop communication fault will be trigged after scanning phase is finished If one loop is disabled panel will skip scanning this loop If all loops are disabled which is not a normal behavior panel will not scan any loop and general disabled LED will be on By default loop 1 i...

Страница 14: ...ons it has the ability to silence the trigged alarms re sound the silenced alarm and perform fire reset Also it can trigger Evacuate key on the panel Access level 2 users can also access panel programming configuration menus through Menu key on the panel Users can only see all panel configuration data but they cannot make any changes to it Access level 3 is the highest secure level and is protecte...

Страница 15: ...is requested from programming menus Only loops fault and loop devices fault will be triggered after scanning is finsihed Any other fire or fault conditions will be ignored PC state This panel mode is valid when computer software starts to update part or all of panel configuration data Panel will not enter PC mode if it has one or more fire conditions If panel has one or more fault conditions it wi...

Страница 16: ...Loop faults Loop devices faults Power faults and onboard sounder faults Panel will change its LCD staus message to fault status only if there is no fire or manual evacuate conditions in the panel Fire conditions always override any fault or manual evacuate conditions Evacuate conditions always override any fault conditions 5 3 LCD icons HST HP201 2 has 8 different LCD icons used to show some infor...

Страница 17: ...on Note that after loop scan default name which is given to loop device is NODE XXX XXX represents the ID of the device So NODE 009 is the name of the loop device not it s ID Name can be changed using programming menus After first fire field there are 3 lines to show different fire fault or manual evacuate conditions based on which tab is highlighted at the bottom You can switch between different ...

Страница 18: ... fault or evacuate The right number is total number of fire fault and evacuate condition in the whole panel For example if the panel detects 7 fire conditions and 9 fault conditions and 2 manual evacuate conditions So when fire tab is selected the numbers will be 007 018 When fault tab is selected the numbers will be 009 018 When evacuate tab is selected then number will be 002 018 ...

Страница 19: ...acuate ID of the condition and total number of conditions with same type Second line contains name of the module and its type Third line contains ID of the module its loop in case of loop devices and its zone Fourth line contains date and time of initiation For loop devices fault first line will contain also type of fault Use up and down arrow keys to go to details of the next condition of the sam...

Страница 20: ...r loop faults and sounder faults LCD icon will not contain which loop or sounder has the fault To know which ID go to sounders config sub menu inside on board config menu or loops config sub menu inside loops config menu Icon is displayed in front of faulty sounder or loop Type of fault open circuit short circuit or communication fault for loops is only known from event status sub menu inside syst...

Страница 21: ...nd silence alarm icon disappears from LCD Alarms stop with fire reset For any onboard output module and loop output module its configuration activates with fault actions it will not be silenced by Silence Alarm key It stops only with fire reset You can re sound activated alarms by pressing Resound Alarm key at access level 2 Silenced alarms will trigger again with any new fire conditions based on ...

Страница 22: ...from the numeric keypad System configuration This menu is used to configure and display general functions of the panel On board configuration This menu is used to configure and display all the onboard circuits on the panel Loops configuration This menu is used to configure and display all loop and devices relates settings Also it is used to configure and display all zones related settings Advanced...

Страница 23: ... onboard coin battery is mounted in its place in the main board even if the main power supply terminals and the backup batteries are removed Panel date will be lost if coin battery is removed and will return to the initial panel date Monday 01 Jan 2007 2 Set time To select this item use arrow keys to highlight it and press ENTER key or press 2 key from numeric keypad This menu is used to update pa...

Страница 24: ...d Enter new 4 digits password Password must be entered twice for configuration After entering 4th digit of the password enter the same password again It will be written on a separate line on the display Character will be displayed on the screen for each digit To save the new level 2 password enable key must be turned on Press ENTER key If panel is at level 3 access state new level 2 password will ...

Страница 25: ...m use arrow keys to highlight it and press ENTER key or press 5 key from numeric keypad This menu is used to change some generic fire alarm related configurations For each configuration item if X symbol is displayed this means that the function is active If X symbol is not displayed this means that the function is not active To change one configuration item use arrow keys to highlight it and press...

Страница 26: ...out the memory used to store the different panel log events First line displays the total number of records the panel can store Second line displays the current used records from memory Third line displays the total number of free records 7 View events To select this item use arrow keys to highlight it and press ENTER key or press 7 key from numeric keypad This menu is used to display stored panel...

Страница 27: ... highlight it and press ENTER key or press 1 key from numeric keypad This menu is used to configure all panel onboard relays You can select any relay using arrow key and press ENTER key on the highlighted key or press the key number directly from numeric keypad All relays have the same configuration Only default settings may be different for some relays ...

Страница 28: ...acts to NC State when Silence Alarm key is pressed or will keep its contacts to NO state even if Silence Alarm key is pressed To change it highlight it with arrow keys and press 0 key If X symbol appears in front of it this means that the relay will stop with silence alarm state If X symbol does not appear in front of the event this means that the relay will not stop with silence alarm state Fourt...

Страница 29: ... If panel is at access level 3 new data will be saved directly If panel is at access level 2 window appears to enter access level 3 password to proceed with saving 2 Sounders configuration To select this item use arrow keys to highlight it and press ENTER key or press 2 key from numeric keypad This menu is used to configure all panel onboard sounder lines You can select any sounder line using arro...

Страница 30: ...he sounder line will be function or not regardless of the current panel state To change it highlight it with arrow keys and press 0 key If X symbol appears in front of it this means that the sounder line will be disabled and not working If X symbol does not appear in front of it this means that the sounder line will be working normally If disabled is active after saving general disabled and sounde...

Страница 31: ...ectly from numeric keypad All dry inputs have the same configuration Only default settings may be different for some dry inputs X Icon in front of a dry input means that this dry input is in disabled state After selecting one dry input dry inputs configuration window appears with its last saved parameter value First configuration is dry input name It will be displayed on the main screen when this ...

Страница 32: ...s not appear in front of it this means that the dry input will be working normally If disabled is active after saving general disabled LED will be on Fourth configuration is zone number Zone for on board dry input is fixed to zone 0 and cannot be changed Fifth configuration is delay value Delay value for inputs is fixed to 0 which mean that dry inputs will trigger immediately when activated After ...

Страница 33: ...put module Function keys are latched when pressed Only fire reset action deactivates its effect Third configuration is disabled state of the function key It means that if the function key will trigger its event when pressed or will do nothing whatever is pressed or not To change it highlight it with arrow keys and press 0 key If X symbol appears in front of it this means that the function key will...

Страница 34: ...r of connected devices for all loops then total number of inputs devices for all loops detectors call point then total number of output devices for all loops output modules loop sounders After that loops are displayed line by line Same information for devices is displayed but for each loop only At the end of each loop line if there is Symbol it means that this loop has at least one loop fault If t...

Страница 35: ...eter value First configuration is loop name It is only used for loop identification and will not be shown on the display To change it highlight it will arrow keys and press 0 key On screen keyboard will be shown at the top right corner of the display Working with it is exactly same as described in changing panel name section Second configuration is disabled state of the loop When loop is disabled ...

Страница 36: ...ght it and press ENTER key or press 3 key from numeric keypad This menu is used to configure loop devices After entering this menu loop selection menu appears to select the loop holds this device If loop is disabled it will not be shown and device configuration cannot be done from panel After loop selection Devices connected to this loop will be shown in a table format One table is 8 rows x 11 col...

Страница 37: ...device will trigger on this event If X symbol does not appear in front of the event this means that the device will not trigger on this event Selection of more than one event is accepted Third configuration is the silence state of the device For input devices it is not shown For output devices it means that if the device will deactivate when Silence Alarm key is pressed or will keep active even if...

Страница 38: ...r the new delay value A new small window appears beside the last delay value Press ENTER key after entering the new delay value If value is accepted it will be shown If value is wrong X symbol appears beside the wrong value While entering the new delay value press EXIT key to cancel entering a new delay value After finishing updates of configuration enable key must be on to save the new values Pre...

Страница 39: ...ging panel name section Second configuration is disabled state of the zone When zone is disabled all devices modules attached to this zone will be in disabled state It will perform exactly as if it is disabled from its configuration menu To change disabled state highlight it with arrow keys and press 0 key If X symbol appears in front of it this means that zone is disabled If X symbol does not app...

Страница 40: ...lected loop is written at the upper right of the window You can exit this menu to the previous menu by pressing ENTER or EXIT key 6 Disabled zones To select this item use arrow keys to highlight it and press ENTER key or press 6 key from numeric keypad This menu is used to show disabled panel zones Disabled zones ID are written in a table format One table is 8 rows x 11 columns So window displays ...

Страница 41: ...rn To select this item use arrow keys to highlight it and press ENTER key or press 1 key from numeric keypad This menu is used to scan all panel enabled loops and save all connected devices with its default settings Current saved devices will be removed from panel memory Press ENTER key to start scanning ...

Страница 42: ... the screen for each digit To save the new level 3 password enable key must be turned on Press ENTER key to save the new password 3 Clear events To select this item use arrow keys to highlight it and press ENTER key or press 3 key from numeric keypad This menu is used to remove all saved log events Press ENTER key to confirm removal 4 Panel reset To select this item use arrow keys to highlight it ...

Страница 43: ...August 2015 Page 43 settings Panel will start to restore all its data and when finished it will display reset complete message on the display Panel will wait 5 seconds and then it will restart itself ...

Страница 44: ... Evacuate Silence state Selected Zone 0 Output Delay 0 11 Relay2 Actions Fault Silence state Not selected Zone 0 Output Delay 0 12 Relay 3 Actions Fire Evacuate Silence state Selected Zone 0 Output Delay 0 13 Sounder line 1 Actions Fire Evacuate Silence state Selected Zone 0 Output Delay 0 14 Sounder line 2 Actions Fire Evacuate Silence state Selected Zone 0 Output Delay 0 15 Input 1 Name DC 1 Act...

Страница 45: ...August 2015 Page 45 Zone 1 21 Output loop devices Actions Fire Evacuate Silence state Selected Zone 1 Output Delay 0 ...

Отзывы: