5.2.4 Mounting the draw lead bolt (option)
Fig. 11: Mounting the draw lead bolt
Item
Part
Item
Part
1
Draw lead bolt
2
Pulling wire/pulling rod
► Lower the bushing slowly onto the transformer.
►
NOTICE
Material damage caused by pulling elements being too big
If the pulling elements (pulling wire or pulling rod) are too big, the O-rings may suffer
damage when the draw lead bolt is pulled through.
► Ensure that the pulling elements (including their fixings on the draw lead bolt) have
a diameter less than 30 mm.
Whilst lowering, pull the draw lead bolt (1) up through the central tube with a pulling wire
or a pulling rod until the draw lead bolt protrudes from the bushing head.
Range STARIS®-Sia+