Sensor Type (Scaling) Table
The user configurable Sensor Type table allows up to 16 different sensor scalings to be configured prior
to defining the point data base. The table elements are as follows:
Mult1 (units multiplier)
Mult10
(10’s
multiplier)
InputBase
(intercept)
By entering
S
the scaling table is revealed. Customisation can be made directly over HyperTerminal or
by download of a configuration file taken from the address calculator tool.
While displaying the table, using a row/column address matrix, each value in the table may be
customized.
For instance, to change Type 1 (row 1) so that it is applicable for °F instead of °C then:
1) Slope of 0.25
a. Units multiplier = 25 therefore enter 13=25 (row#column#=25)
b. Shift decimal place left two places = -2 therefore enter 12=-2
2) Intercept of -48
a. Input Base = Intercept / Slope = -48/.25 = -192 therefore enter 11=-192
Row 0
Row 15
Column 3