background image

 
 
 
 
 

HRW HPE-BNP1BUS V401 Manual 120201.doc            E. & O. E. / Subject to change without notice 

Page 5 of 18 

Additional Settings 

Some PC platforms may need keyboard response adjustment for initial Terminal Mode success. These 
settings may be done via the PC Control Panel >> Keyboard Settings: 
 

  Fastest Repeat rate 

  Shortest Delay time 

  Fastest Cursor Blink rate 

Connecting at 76800 Baud Rate 

Because HyperTerminal does not support 76800 baud then after setting to 76800 the device baud rate 
will remain at 9600 baud for HyperTerminal communication and switch to 76800 after Writing the new 
baud rate and eXiting terminal mode. 
 
To allow later terminal communication a device set with 76800 baud will operate at 9600 baud for the 
first 5 seconds after a power-up. If no attempt to connect the terminal at 9600 baud is made within 5 
seconds of a power-up then the device will automatically switch to 76800 for normal network operation. 

Saving HyperTerminal Settings 

 
For ease of connection it is recommended to save the HyperTerminal setup for each baud rate you may 
wish to use with an easily recognised configuration name. For example: 
 

 HPECOM 

24 

(2400) 

 HPECOM 

48 

(4800) 

 HPECOM 

96 

(9600) 

  HPECOM 19.2 (19200) 

  HPECOM 38.4 (38400) 

  HPECOM 57.6 (57600) 

 

Break in to Terminal Mode 

When HyperTerminal is running and the HPECOM cable is connected to the device the initial terminal 
screen will be receiving an ASCII character dump which is the BACnet transmission from the device. 
The ASCII dump will appear differently with different device address setting and if HyperTerminal baud 
rate is different to the baud rate set in the device. Below is an illustration of how the ASCII dump will 
look for a device at default settings; address 98 and 9600 baud. 
 

 

 
To break in to terminal mode set Caps Lock on and hold the 

‘T’

 character key continuously 

(TTTTTTT…). After five (5) T’s have been sent to the device it will switch to terminal mode. At this point 
the BACnet activity on the network will be halted and the device will display the default user screen. 

Содержание HPE-BNP1BUS

Страница 1: ...ed to the gateway for read write access of up to 250 data points Typical Applications BACnet MS TP network integration of P1 devices System 600 APOGEE Insight TEC ATEC SCU DPU DLM MEC Point Expansion units HRW HP P1 devices Feature Summary FIND function for initial network device application identification Diagnostic function for comms verification and trouble shooting Continuous poll for point st...

Страница 2: ...IN TO TERMINAL MODE 5 BACNET CONFIGRATION COMMANDS 6 P1 CONFIGURATION COMMANDS 7 P1 INTEGRATION 8 FIND 8 SENSOR TYPE SCALING TABLE 9 Standard Sensor Types 10 POINT TYPE 10 DATA POINT CONFIGURATION 10 DATA BASE MAPPING TOOL 12 POINT CONFIGURATION 12 SCALING TABLE CONFIGURATION 13 DOWNLOAD TEXT FILE 14 SCAN P1 FLN NETWORK 14 DIAGNOSTIC DISPLAY 14 INSTALLATION COMMISSIONING 15 CONNECTIONS 16 DIMENSIO...

Страница 3: ...It is important to have the P1 device manufacturer s manual available to assist with P1 point address and type scaling Each point of the gateway data base consists of 1 Device addresses 2 Point numbers within the device addresses 3 Sensor type relating to each point as defined in the scaling table 4 A point type LDI LDO LAI LAO represented as a number 1 4 respectively BACnet Priority Array The BAC...

Страница 4: ...ue are recommended A USB port Serial comm port DB9 converter may be required for HPECOM if the PC being used does not include a Com 1 serial port The following settings reflect HyperTerminal Please contact us if you require assistance setting up Indigo HyperTerminal Settings For successful communication between HyperTerminal and the device initial Properties setup of HyperTerminal should be as per...

Страница 5: ...rk operation Saving HyperTerminal Settings For ease of connection it is recommended to save the HyperTerminal setup for each baud rate you may wish to use with an easily recognised configuration name For example HPECOM 24 2400 HPECOM 48 4800 HPECOM 96 9600 HPECOM 19 2 19200 HPECOM 38 4 38400 HPECOM 57 6 57600 Break in to Terminal Mode When HyperTerminal is running and the HPECOM cable is connected...

Страница 6: ... it will be necessary to reconnect with HyperTerminal at the new comm speed to save write the change Set Maximum Master address MM 1 127 Highest Master device address on the network is registered Next address searching limited to MM address Set Sys Vendor ID SysVid SV 0 255 System vendor specific features may be available SV 0 applies generic BACnet operation If an entered ID is not implemented th...

Страница 7: ...int to NULL R 4 253 Specified point is Released to NULL priority 17 will be displayed at the extreme right of the target data point configuration line to signify NULL priority Enable P1 subnet communication E Toggles Enabled Disabled of M Bus Subnet communication Default Disabled to allow easy configuration when no M Bus devices are connected Always Enable when M Bus devices are connected and poin...

Страница 8: ... to decide which points are available in each P1 device simplifying the creation of the point database of the gateway Enter F to start the Find function The Find function will automatically poll each possible P1 address to find how many devices are on an existing network Each address is polled twice in the event a device does not respond on it s first polling Once devices are identified they will ...

Страница 9: ...able is revealed Customisation can be made directly over HyperTerminal or by download of a configuration file taken from the address calculator tool While displaying the table using a row column address matrix each value in the table may be customized For instance to change Type 1 row 1 so that it is applicable for F instead of C then 1 Slope of 0 25 a Units multiplier 25 therefore enter 13 25 row...

Страница 10: ...HRW 14 Digital Normally Closed 1 0 Type 15 HRW 15 Digital Toggle 1 0 Point Type Point Type programming value defines the P1 point in the gateway so that the gateway knows what BACnet object type should be used when making the point data available on the BACnet MSTP network P1 Point Type Description Gateway Point Type Gateway Tag BACnet Object Type LDI Digital Input 1 DI BV LDO Digital Output 2 DO ...

Страница 11: ... by default indicted by value 17 on the right side of the display To command from the BACnet BMS then commands must be sent with a priority of 16 or higher After downloading your point database and connecting the network always remember to Enable the P1 network comms and Write the Enabled state so that comms is automatically reinstated after a power failure Normally the gateway will poll the netwo...

Страница 12: ...ich can be downloaded to the gateway as a text file txt Point Configuration In the example below two P1 devices are configured each with three input points to be read Once the information is properly entered in the tool the resultant point configuration data in the Download column may be copied to Notepad for saving as a text file and download to the gateway The last row of the download data 10000...

Страница 13: ...he Download column This download data is then copied to a text file for download over HyperTerminal using the same process as used for the point database download The reference Slope and Intercept values are taken from the P1 device documentation Entering these two values automatically calculates the Base value required by the HPE BNP1BUS The 10 s Multiplier and 1 s Multiplier values must be manua...

Страница 14: ...rminal mode any scanning of the P1 network will only occur after pressing Enter as a separate action to any other settings After exit from terminal mode the scanning will occur automatically After pressing Enter wait for the display to refresh with read values this may take some time if the network contains many devices and data points Diagnostic Display For trouble shooting the Diagnostic functio...

Страница 15: ...en at each device should be continuously connected via the S terminal of the device note that the device s S terminal has no electrical connection to the device it merely acts as a junction terminal for the purpose of screen continuity The RS485 cable should avoid cable routes that run with power cables Where the RS485 cable must cross power cables then they should cross at 90 avoiding parallel ru...

Страница 16: ...c E O E Subject to change without notice Page 16 of 18 Connections Dimensions If using HDA0002 DIN rail adapter brackets the overall depth from the gear plate to the front surface of the device is 45 5mm P1 Network BACnet RS485 HPE BNP1BUS ...

Страница 17: ...int gateway BACnet MS TP integration of P1 FLN devices for control panel mounting Standard package 40 units per carton Accessories HDA0002 DIN rail adapter brackets factory fitted HPECOM Configuration cable DB9 RJ11 HPECOMU Configuration cable USB RJ11 U232 P9 RS232 DB9 USB adapter cable Other HP_BN Series Devices HPC0662BN Universal Controller 12 Point BACnet MS TP 24Vac HPC8884BN Universal Contr...

Страница 18: ...HRW HPE BNP1BUS V401 Manual 120201 doc E O E Subject to change without notice Page 18 of 18 Notes ...

Отзывы: