Chapter 6 Function Introduction
HD20 Series Inverters User Manual
―
77
―
No.
Name Description
Range
【
factory setting
】
F13.51
Reserved
F13.52
Reserved
6.2.15 Group F14 Reserved
6.2.16 Group F15 Digital I/O Terminal Parameters
No.
Name Description
Range
【
factory setting
】
F15.00
DI1 terminal function selection
0
-
86
【
2
】
F15.01
DI2 terminal function selection
0
-
86
【
3
】
F15.02
DI3 terminal function selection
0
-
86
【
0
】
F15.03
DI4 terminal function selection
0
-
86
【
0
】
F15.04
DI5 terminal function selection
0
-
86
【
0
】
F15.05
DI6 terminal function selection
0
-
86
【
0
】
F15.06
Reserved
F15.07
Reserved
F15.08
Reserved
0: Reserved. It disables the terminal’s function. The inverter ignores the signal input via this terminal.
• The unwanted terminal is recommended to be set as 0 so as to avoid wrong connection or
action.
1: Inverter enabled.
• When enabled, the inverter is enabled to run;
• When disabled, the inverter is disabled to run and will be in auto stop status.
• If no terminal selects this function, it defaults that the inverter is enabled.
2,3: FWD/REV function. You can set any multi-function terminal for the FWD/REV terminal to control
the inverter’s run and stop.
• When F00.11 = 1 (external terminal reference run command source) or terminal No. 11 function
is enabled, FWD/REV function is valid.
• Refer to parameter F15.16.
4: Three-wire operation mode.
• Refer to parameter 15.16.