Earthed Metal Back Plate
to suit HL/HEE Flush Load Centres
Cat. HL12FS-BP, HEE18FS-BP, HL24FS-BP, HL36FS-BP, HL48FS-BP
Instruction Manual
1
Range
Reference : AS3000:2007 wiring rules requirement (Clause : 3.9.4.4 (b).
2
3
Standards
Step 1:
Position the plate so that
overhang is on the side of the
incoming cable. Mark drilling
holes to fix the plate on back of
the enclosure with the help of
pre-drilled holes on back plate
(5 holes to mark : 4 c
earth).
Part No
A
(mm)
B
(mm)
Thickness
(mm)
to suit
enclosure
HL12FS-BP
425
265
0.9
HL12F
HEE18FS-BP
367
384
0.9
HEE18F
HL24FS-BP
550
265
0.9
HL24F
HL36FS-BP
675
265
0.9
HL36F
HL48FS-BP
800
265
0.9
HL48F
B
A
Installation
Step 2:
Drill with 4mm bit on back of the
enclosure.
Step 3:
Fix back plate to enclosure using
bolts, washers & nuts provided.
Make sure the overhang is
covering unprotected cables (top
or bottom).
Step 4:
Fix 4mm² earth strap to the earth
bar and stud (overhang portion on
the side of the earth terminal)
Metal plate back
Flush enclosure