Fan and thermal issues
General fan issues
Symptom
Fan not operating as expected.
Cause
• The fans are not seated properly.
• The fan configuration does not meet the functional requirements of the server.
• The server is not ventilated properly.
• One or more required fans are not installed.
• Required fan blanks are not installed.
• Error messages are displayed during POST or in the IML.
• One or more fans are not functioning.
Action
1.
Be sure the fans are properly seated and working:
a.
Follow the procedures and warnings in the server documentation for removing the access panels
and accessing and replacing fans.
a.
Unseat, and then reseat, each fan according to the proper procedures.
b.
Replace the access panels, and then attempt to restart the server.
2.
Be sure the fan configuration meets the functional requirements of the server.
3.
Be sure no ventilation issues exist. If the server is operated for an extended period of time with the
access panel removed, airflow might be impeded, causing thermal damage to components.
4.
Be sure no POST error messages are displayed while booting the server that indicate temperature
violation or fan failure information.
5.
Use iLO or an optional IML viewer to access the IML to see if any event list error messages relating
to fans are listed.